Mitsubishi Electronics FX3G User Manual

Page of 964
696
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
30 External Device Communication – FNC270 to FNC276
30.6 FNC275 – IVMC / Inverter Multi Command
3. Related devices
→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.
*1.
Cleared when PLC power supply is turned from OFF to ON.
*2.
Cleared when the PLC mode switches from STOP to RUN.
*3.
Initial value: -1
Cautions
→ For other cautions, refer to the Data Communication Edition manual.
• It is not permitted to use an "RS (FNC 80)/RS2 (FNC 87)"/"ADPRW (FNC276)"/"FLCRT (FNC300) to FLSTRD 
(FNC305)" instruction and an "IVCK (FNC270) to IVMC (FNC275)" instruction for the same port.
• Two or more inverter communication instructions (FNC270 to FNC275) can be driven for the same port at the same 
time.
• Number of occupied devices
Two devices are occupied respectively by 
 and 
.
Make sure not to use those devices in another control.
• If a device number outside the range due to indexing, etc. is specified in 
, the receive data from the inverter 
is not stored in 
. However, values set in 
 and 
+1 may be written to the inverter.
• If any unspecified value is set in 
, unexpected data may be written to and read from the inverter, and values 
of  
and +1 
may 
be 
updated.
• IVMC instruction reads the inverter status at the time of communication with the inverter, and stores the read status 
to 
. Accordingly, the status written by the IVMC instruction can be read by a next or later read instruction 
(IVCK or IVMC).
Applicable inverters
This instruction is applicable to the following inverters: 
- FREQROL-E700 (February 2009 and later)
- FREQROL-D700 (Applicable in all)
→ For details, refer to the respective inverter manual
Applicable programming tool
This instruction is applicable to the following programming tools: 
• FX
3S
 Series PLC
• FX
3G
 Series PLC
• FX
3GC
 Series PLC
• FX
3U
/FX
3UC
 Series PLCs
Number
Description
Number
Description
ch1
ch2
ch1
ch2
M8029
Instruction execution complete
D8063 D8438 Error code of serial communication error
*1
M8063 M8438 Serial communication error
*1
D8150 D8155 Response wait time in inverter communication
*1
M8151 M8156 Inverter communicating
D8151 D8156 Step number in inverter communication
*3
M8152 M8157 Inverter communication error
*2
D8152 D8157 Error code of inverter communication error
*2
M8153 M8158 Inverter communication error latch
*2
D8153 D8158 Latch of inverter communication error occurrence step
*2*3
M8154 M8159 Inverter instruction error
*2
D8154 D8159 IVBWR instruction error parameter number
*2*3
Product name
Model name
Compatible Versions
Remarks
GX Works2
SW†DNC-GXW2-E
Ver. 1.492N or later
-
FX-30P
Ver. 1.50 or later
Product name
Model name
Compatible Versions
Remarks
GX Works2
SW†DNC-GXW2-E
Ver. 1.62Q or later
-
FX-30P
Ver. 1.50 or later
Product name
Model name
Compatible Versions
Remarks
GX Works2
SW†DNC-GXW2-E
Ver. 1.77F or later
-
FX-30P
Ver. 1.50 or later
Product name
Model name
Compatible Versions
Remarks
GX Works2
SW†DNC-GXW2-E
Ver. 1.48A or later
-
FX-30P
Ver. 1.20 or later
  
S
3
   
D
   
D
   
D
  
S
3
  
S
3
  
S
2
   
D
   
D
   
D