Mitsubishi Electronics FX3G User Manual

Page of 964
826
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
PLC Mode
 M 8030
*1
Battery LED
OFF
When M8030 set to ON, LED on PLC is not lit
even if battery voltage low is detected.
Refer to Subsection 37.2.10.
 M 8031
*1
Non-latch memory
all clear
If this special auxiliary relay is activated, the
ON/OFF image memory of Y, M, S, T, and C,
and present values of T, C, D, special data
registers
*3
, and R
*2
 are cleared to zero.
However, file registers (D) in program memory
and extension file registers (ER)
*2
 in the
memory cassette are not cleared. 
Refer to Subsection 37.2.12.
 M 8032
*1
Latch memory
all clear
 M 8033
Memory hold
STOP
When PLC is switched from RUN to STOP,
image memory and data memory are retained.
Refer to Subsection 37.2.13.
 M 8034
*1
All outputs disable
All external output contacts of PLC are turned
OFF.
Refer to Subsection 37.2.14.
 M 8035
Forced RUN mode
Refer to Subsection 37.2.15 for details.
 M 8036
Forced RUN signal
 M 8037
Forced STOP
signal
[M]8038
Parameter setting
Communication parameter setting flag
(for N:N network setting)
Refer to Data Communication Edition.
D8176 to 
D8180
*4
 M 8039
Constant scan
mode
When M8039 is ON, PLC waits until scan time
specified in D8039 and then executes cyclic
operation.
Refer to Subsection 37.2.16.
D8039
*1.
It is executed when END instruction is executed.
*2.
R and ER are available only in FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 PLCs.
*3.
Special data registers are not cleared in FX
1S
/FX
1N
/FX
1NC
/FX
2N
/FX
2NC
 PLCs.
*4.
It is available in Ver. 2.00 or later.
Number and 
name
Operation and function
Applicable model
FX
3S
FX
3G
FX
3GC
FX
3U
FX
3UC
Correspond-
ing special 
device
FX
1S
FX
1N
FX
1NC
FX
2N
FX
2NC