Mitsubishi Electronics FX3G User Manual

Page of 964
827
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
31
FNC277
-F
NC2
79
Da
ta
 
Trans
fer 3
32
FNC28
0-F
NC
289
H
igh-Speed 
Process
ing 2
33
FNC2
90-
FNC299
Ex
tensi
on Fi
le
 
Register C
ontrol
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt 
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
Inform
ati
on
B
Ex
ecuti
on
 T
imes
Step Ladder and Annunciator (Refer to ANS (FNC 46), ANR (FNC 47), IST (FNC 60), and Chapter 35 for details.) 
 M 8040
Transfer disable
While M8040 is turned ON, transfer between
states is disabled.
[M]8041
*1
Transfer start
Transfer from initial state is enabled in
automatic operation mode.
[M]8042
Start pulse
Pulse output is given in response to a start
input.
 M 8043
*1
Zero return complete
Set this in the last state of zero return mode.
 M 8044
*1
Zero point condition
Set this when machine zero return is detected.
 M 8045
All output reset 
disable
Disables the ’all output reset’ function when the
operation mode is changed.
[M]8046
*2
STL state ON
ON when M8047 is ON and any state S0 to
S899 or S1000 to S4095
*3
 is active.
M8047
 M 8047
*2
STL monitoring 
enable
D8040 to D8047 are enabled when M8047 is
ON.
D8040 to 
D8047
[M]8048
*2
Annunciator
operate
ON when M8049 is ON and any annunciator
S900 to S999 is ON.
 M 8049
*1
Annunciator enable
D8049 is enabled when M8049 is ON.
D8049
M8048
*1.
Cleared when the PLC switches from RUN to STOP.
*2.
Executed at END instruction.
*3.
S1000 to S4095 are available only in the FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series PLCs.
Interrupt Disable (Refer to Subsection 36.2.1.) for details.
M8050 
(input interrupt)
I00  disable
*4
If an input interrupt or timer interrupt occurs
while a special auxiliary relay for that
interrupt (M8050 - M8058) is ON, the
interrupt will not operate.
For example, turning M8050 ON disables
the I00  interrupt; hence, the interrupt
routine is not processed even in an
allowable program area.
If an input interrupt or timer interrupt occurs
while a special auxiliary relay for that
interrupt (M8050 - M8058) is OFF, 
a) The interrupt will be accepted.
b) The interrupt routine will be processed
promptly if it is permitted by the EI
(FNC 04) instruction. However, if the
DI (FNC 05) instruction disables
interrupts, the interrupt program will
not be processed until EI (FNC 04)
permits the interrupts.
M8051 
(input interrupt)
I10  disable
*4
M8052 
(input interrupt)
I20  disable
*4
M8053 
(input interrupt)
I30  disable
*4
M8054 
(input interrupt)
I40  disable
*4
M8055 
(input interrupt)
I50  disable
*4
M8056 
(Timer interrupt)
I6
 disable
*4
M8057 
(Timer interrupt)
I7
 disable
*4
M8058 
(Timer interrupt)
I8
 disable
*4
M8059
Counter interrupt 
disable
*4
Interrupt of I010 to I060 disabled
*4.
Cleared when the PLC switches from RUN to STOP.
Number and 
name
Operation and function
Applicable model
FX
3S
FX
3G
FX
3GC
FX
3U
FX
3UC
Correspond-
ing special 
device
FX
1S
FX
1N
FX
1NC
FX
2N
FX
2NC