Mitsubishi Electronics FX3G User Manual
845
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
Series
Programming Manual - Basic & Applied Instruction Edition
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
31
FNC277
-F
NC2
79
79
Da
ta
Trans
fer 3
fer 3
32
FNC28
0-F
NC
289
289
H
igh-Speed
Process
ing 2
33
FNC2
90-
FNC299
FNC299
Ex
tensi
on Fi
le
le
Register C
ontrol
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
p
Inform
ati
on
B
Ex
ecuti
on
T
imes
Stepladder and Annunciator
[D]8040
*1
ON state number 1
The smallest number out of active state
ranging from S0 to S899 and S1000 to
S4095
ranging from S0 to S899 and S1000 to
S4095
*2
is stored in D8040 and the second-
smallest state number is stored in D8041.
Active state numbers are then sequentially
stored in registers up to D8047 (Max. 8
points).
Active state numbers are then sequentially
stored in registers up to D8047 (Max. 8
points).
M8047
[D]8041
*1
ON state number 2
[D]8042
*1
ON state number 3
[D]8043
*1
ON state number 4
[D]8044
*1
ON state number 5
[D]8045
*1
ON state number 6
[D]8046
*1
ON state number 7
[D]8047
*1
ON state number 8
[D]8048
Not used
–
–
–
–
–
–
–
–
–
–
–
[D]8049
*1
On state minimum
number
number
When M8049 is ON, the smallest number out
of active annunciator relay ranging from S900
to S999 is stored in D8049.
of active annunciator relay ranging from S900
to S999 is stored in D8049.
–
M8049
–
–
–
[D]8050 to [D]8059 Not used
–
–
–
–
–
–
–
–
–
–
–
*1.
Executed at END instruction.
*2.
S1000 to S4095 are available only in FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLCs.
Error Detection (Refer to Chapter 38 for details.)
[D]8060
If the unit or block corresponding to a
programmed I/O number is not actually loaded,
M8060 is set to ON and the first device number
of the erroneous block is written to D8060.
programmed I/O number is not actually loaded,
M8060 is set to ON and the first device number
of the erroneous block is written to D8060.
–
M8060
–
–
–
[D]8061
Error code for PLC hardware error
M8061
–
–
–
[D]8062
Error code for PLC/PP communication error
M8062
Error code for serial communication error 0 [ch0]
*4
–
–
–
M8062
–
–
–
–
–
[D]8063
*5
Error code for serial communication error 1 [ch1]
M8063
[D]8064
Error code for parameter error
M8064
[D]8065
Error code for syntax error
M8065
[D]8066
Error code for ladder error
M8066
[D]8067
*6
Error code for operation error
M8067
D 8068
Operation error step number latched
*7
*7
M8068
[D]8069
*6
Error step number of M8065 to M8067
*8
*8
M8065 to
M8067
*3.
10 to 337 in FX
3U
/FX
3UC
/FX
2N
/FX
2NC
PLCs, and 10 to 177 in FX
3G
/FX
3GC
PLCs.
*4.
Cleared when PLC power supply is turned from OFF to ON.
*5.
The operation varies according to PLC:
-
-
Cleared in an FX
1S
/FX
1N
/FX
1NC
/FX
2N
/FX
2NC
when PLC switches from STOP to RUN.
-
Cleared in an FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
PLCs when PLC power supply from OFF to ON.
*6.
Cleared when PLC switches from STOP to RUN.
*7.
In case of 32K steps or more, step number is stored in [D8313, D8312].
*8.
In case of 32K steps or more, step number is stored in [D8315, D8314].
Number and
name
Content of register
Applicable model
FX
3S
FX
3G
FX
3GC
FX
3U
FX
3UC
Correspond-
ing special
device
FX
1S
FX
1N
FX
1NC
FX
2N
FX
2NC
1 0 2 0
1: Input X 0: Output Y
Device number
ample: If X020 is unconnected.
BCD converted value
*3
1 0 2 0
1: Input X 0: Output Y
Device number
Example: If X020 is unconnected.
BCD converted value
*3