37 Operation of Special Devices (M8000 -, D8000 -)
37.2 Supplement of Special Devices (M8000 - and D8000 -)
2. Special data register (D8260 to D8279)
• FX
3S
/FX
3G
 PLCs
*1.
In the case of FX
3S
 PLC, all versions are applicable.
*2.
Only to FX
3G
 PLC (40-point and 60-point type) can be connected.
Number
Operation and function
FX
3G
-2AD-BD
FX
3G
-1DA-BD
Applicable 
version
Ver. 1.10 or later
*1
Ver. 1.10 or later
*1
1st analog expansion board
 D 8260
Input data Ch1
Output data
 D 8261
Input data Ch2
Not used
 D 8262
Not used
Not used
 D 8263
Not used
Not used
 D 8264
Number of averaging times for
Ch1 (1 to 4095)
Not used
 D 8265
Number of averaging times for
Ch2 (1 to 4095)
Not used
 D 8266
Not used
Not used
 D 8267
Not used
Not used
 D 8268
Error status
Error status
 D 8269
Model code: K3
Model code: K4
2nd analog expansion board
*2
 D 8270
Input data Ch1
Output data
 D 8271
Input data Ch2
Not used
 D 8272
Not used
Not used
 D 8273
Not used
Not used
 D 8274
Number of averaging times for
Ch1 (1 to 4095)
Not used
 D 8275
Number of averaging times for
Ch2 (1 to 4095)
Not used
 D 8276
Not used
Not used
 D 8277
Not used
Not used
 D 8278
Error status
Error status
 D 8279
Model code: K3
Model code: K4