Mitsubishi Electronics FX3G User Manual

Page of 964
895
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FNC277
-F
NC2
79
Da
ta
 
Trans
fer 3
32
FNC28
0-F
NC
289
H
igh-Speed 
Process
ing 2
33
FNC2
90-
FNC299
Ex
tensi
on Fi
le
 
Register C
ontrol
34
FN
C300-
FNC30
5
FX
3U
-C
F-
AD
P
35
SFC
•STL
Programming
36
Interrupt 
Function
37
Sp
ec
ia
l D
evi
ce
38
E
rror Code
A
Ve
rsi
on U
Inform
ati
on
B
Ex
ecuti
on
 T
imes
Serial communication error 1 [M8063(D8063)]
0000
No error
6301
Continues
operation
Parity, overrun or framing error
Ethernet communication, inverter communication, 
computer link and programming:
Ensure the parameters are correctly set according to 
their applications.
N:N network, parallel link, MODBUS communication, 
etc.:
Check programs according to applications.
Remote maintenance:
Ensure modem power is ON and check the settings of 
the AT commands.
Wiring:
Check the communication cables for correct wiring.
6302
Communication character error
6303
Communication data sum check error
6304
Communication data format error
6305
Command error
6306
Communication time-out detected
6307
Modem initialization error
6308
N:N network parameter error
6309
N:N Network setting error
6312
Parallel link character error
6313
Parallel link sum error
6314
Parallel link format error
6320
Inverter communication error
6321
MODBUS communication error
6330
Memory access error
When the memory cassette is used, check whether it is
mounted correctly.
If the problem persists or if the memory cassette is not
used, something may be malfunctioning inside the PLC.
Consult your local Mitsubishi Electric representative.
6340
Special adapter connection error
Check connection of the special adapter.
Parameter error [M8064(D8064)]
0000
No error
6401
Stops
operation
Program sum check error
STOP the PLC, and correctly set the parameters.
Check that the following functions are not used with
an unsupported PLC version when a memory
cassette is attached:
-
Permanent PLC lock (supported in FX
3U
/FX
3UC
 
PLCs Ver. 2.61 or later)
-
Read-protect the execution program for block 
passwords (supported in FX
3U
/FX
3UC
 PLCs Ver. 
3.00 or later)
-
FX
3U
-FLROM-1M (supported in FX
3U
/FX
3UC
 
PLCs Ver. 3.00 or later)
6402
Memory capacity setting error
6403
Latched device area setting error
6404
Comment area setting error
6405
File register area setting error
6406
Special unit (BFM) initial value setting, positioning 
instruction setting sum check error
6407
Special unit (BFM) initial value setting, positioning 
instruction setting error
6409
Other setting error
6411
Built-in CC-Link/LT special function block invalid 
parameter settings (LT-2 dedicated area).
STOP the PLC, and correctly set the parameters.
Set parameters correctly, turn OFF the power, and
then turn ON the power.
6412
Built-in CC-Link/LT special function block parameter 
settings sum check error (special function settings area).
6413
Built-in CC-Link/LT special function block parameter 
settings sum check error (LT-2 dedicated area).
6420
Special parameter sum check error
STOP the PLC, and correctly set the parameters.
Set special parameters correctly, turn OFF the power,
and then turn ON the power.
6421
Special parameters setting error
Check the contents of the special parameter error
code (D8489), confirm troubleshooting for special
adapters/special blocks, and set special parameters
correctly.
Set special parameters correctly, turn OFF the power,
and then turn ON the power.
Error 
code
PLC operation at 
error occurrence
Contents of error
Action