A Programming Tool Applicability and Version Upgrade History
A-1 Programming Tool Applicability
Cautions on writing during RUN
*1.
Circuit blocks cannot be edited to insert a label as shown below when written during RUN.
Item
Caution
Program memory which can be written in 
RUN mode
Built-in RAM and optional memory cassette (whose write protect switch is set to OFF)
Number of 
program steps 
which can be 
written for 
circuit change 
in RUN mode
GX  Works2 
Ver. 1.08J or later
GX  Developer 
Ver. 8.72A or later
For  FX
3S
/FX
3G
/FX
3GC
 PLCs 
256 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks
except final circuit
GX  Works2 
Ver. 1.08J or later
GX  Developer 
Ver. 8.24A or later
For  FX
3U
/FX
3UC
 PLCs Ver. 2.20 or later
256 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks
except final circuit)
For  FX
3UC
 PLC earlier than Ver. 2.20
127 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks
except final circuit)
GX  Developer 
Ver. 8.22Y and 
earlier
FX-PCS/WIN(-E)
127 steps or less after edit (addition/deletion) (including NOP immediately after circuit blocks except 
final circuit)
Circuit blocks which cannot be written 
during RUN
Circuit blocks
*1
 in which labels P and I are added, deleted, or changed in edited circuits
Circuit blocks in which 1-ms timers (T246 to T249 and T256 to T511) are added in edited circuits
Circuit blocks in which the following instructions are included in edited circuits
Instruction to output high-speed counters C235 to C255 (OUT instruction)
SORT2 (FNC149), TBL (FNC152), RBFM (FNC278) and/or WBFM (FNC279) instructions
I001
FNC 04
EI
FNC 06
FEND
Pointer for
interrupt
Label I is inserted by editing the circuit block
FNC 03
IRET
END
Step
0
Added, deleted, or changed
Added, deleted, or changed