Mitsubishi Electronics FX3G User Manual

Page of 964
940
FX
3S
/FX
3G
/FX
3GC
/FX
3U
/FX
3UC
 Series
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-4 Applied Instruction Execution Time
Data move 3
277
278
RBFM
*1
50+900n
0.715
n : Number of points transferred in
one operation cycle
RBFM
*2
244 + 103n
0.715
279
WBFM
*1
24 + 966n
0.715
n : Number of points transferred in
one operation cycle
WBFM
*2
292 + 116n
0.715
*1.
When the instruction is executed to a BFM in a special function unit/block for the FX
0N
/FX
2N
/FX
2NC
 Series or
in the CC-Link/LT built in the FX
3UC
-32MT-LT(-2)
*2.
When the instruction is executed to a BFM in a special function unit/block for the FX
3U
/FX
3UC
 Series
High-speed processing 2
280 HSCT
30.0
1.365
281
282
283
284
285
286
287
288
289
Extension file register control
290 LOADR
13.2 + 0.44n
0.325
291 SAVER
166n
6.4
292 INITR
17600n
0.325
293 LOGR
244 + 17.9n
0.715
294 RWER
46700n
0.325
n : Number of write target 
sectors
295 INITER
17300n
0.325
296 
to 
299
FX
3U
-CF-ADP
300 FLCRT
83.2
6.64
301 FLDEL
49.1
6.32
302 FLWR
77.9 + 2.9n
6.26
n : Number of written data
points
*3
303 FLRD
59.2 + 4.25n
6.18
n : Number of read data
points
*3
304 FLCMD
50.9
6.26
305 FLSTRD
50.9
6.24
*3.
When 16-bit data is written or read.
FNC
No.
Instruction
Execution time in ON status (
µs)
Execution time in OFF status (
µs)
Remarks
16-bit instruction
32-bit instruction
16-bit instruction