Lewmar v700 User Manual

Page of 9
6
V700 Windlass
7
V700 Windlass
GB
  DO NOT use a permanent adhesive/sealant, e.g., 5200
•  Using a 10 mm (
3
/
8
”) diameter drill, make the three holes 
for the mounting studs. With a 65 mm (2
1
/
2
”) diameter hole 
saw, make the hole for the rode to pass throughwith a 115 
mm (4
1
/
2
”) diameter hole saw, make a hole for the motor 
gearbox to pass through.
 
When all the holes have been made, remove the template. To 
help avoid water absorption by the deck, apply an appropriate 
marine sealant to the freshly cut hole edges.
Fig. 1.6-4
•  Place the mounting template on the deck or mounting pad 
in the desired position for the windlass and hold it in place 
using adhesive tape.
•  NOTE: Check the scale of the 
template matches the winch.
Fig. 1.6-5
•  Fully screw the three mounting studs into the base of the 
windlass. This can be done, quite simply, using the multi-tool 
wrench supplied. Screw the studs into the base fi nger tight, 
with the fl ats towards the base as shown (Fig 1.6-5).
•  Next, using the wrench on the fl ats, tighten the studs until 
they bottom out in their holes. Do this to each of the studs 
in turn.
Fig. 1.6-6
 
As a rule of thumb, if the fl ats on the studs are visible below 
deck, the deck and/or any packing is likely to be too thin to 
offer adequate support when the windlass is under load.
•  NOTE: If using silicone or other rubber y type sealant, 
it is advisable to allow curing of the sealant before 
fi nal tightening of the mounting nuts. Trim the studs 
back to 6 mm (
1
/
4
”) below the fully tightened nuts.
2. Electrical wiring installation
2.1 Electric cable selection
To achieve the best performance and to safeguard your electrical 
system it is essential that any electrical windlass be fi tted with 
suffi ciently large diameter cable to cope with the current draw 
imposed upon it and to keep the voltage drop within acceptable 
limits. In any circumstance voltage drop due entirely to cable 
resistance should not exceed 10%.
The following table gives recommended cable sizes. The 
recommendations are based on total length of cable required, 
from the battery, following the route of the cables.
•  Total length of cable run is from the batter y to the 
windlass, and from the windlass back to the batter y.
•  In Multi Station installations 14 AWG wire (1.5 mm² cross 
sectional area, 21/0.30 PVC covered) is used to connect the 
switches to the reversing control box.
2.2 Wiring
Plan the installation to suit the controls and give the operator a full 
view of the windlass. The wiring system should be of the two cable 
fully insulated return type, which avoids possible electrolytic 
corrosion problems. We recommend the use of type III stranded, 
tinned copper wire with copper crimp terminals. Most modern 
installations are negative return (negative ground) but polarity 
should be checked. If necessary add a grounding strap between 
the mounting studs and an earthing point.
•  NOTE: If a Contactor is used in a V700 installation, 
the Contactor must be sited in a dr y location.
If a contactor is installed in an anchor locker it is exposed to harsh 
conditions it is not designed to withstand. Furthermore this type 
of installation will void your warranty.
Overload protection, in the form of the circuit breaker/isolator 
supplied, must be built into the windlass wiring circuit. This 
protects the wiring and prevents undue damage to the windlass 
motor, in the event of its being stalled by an excessive load in 
service.
It is advisable to site the circuit breaker/isolator in a dr y, 
readily accessible place. The Breaker/ Isolator supplied must 
be manually reset should an overload occur that causes it to trip 
to the off position.
•  NOTE: Crimp terminals should be used on all wire 
ends wherever possible for good electrical contacts.
If you are not sure you understand these guidelines, seek 
professional help. Ensure that the installation complies with 
USCG, ABYC, NMMA or other local regulations.
2.3 Control switch installation
Follow the mounting instructions supplied with the switch. 
Remember, in a Multi Station installation all switches must be 
wired in a parallel circuit.
  DO NOT confuse cable Length with the length of the vessel!
  DO NOT install the contactor in the anchor locker.
Fig. 1.6-3
•  Place the base mat in position on the deck, optionally, apply 
a suitable sealant to the base of the windlass, any mounting 
pad or around the studs.
Fig. 1.6-7
Boat Length
Cable Length 
Up To
Cable Size
(m)
(ft)
(m)
(ft)
(AWG)
(mm
2
)
7.5
25
0 - 10
0 - 33
8
10
9
30
11 - 18
34 - 60
6
16
10.5
35
19 - 24
61 - 80
4
25