PVI Industries 1000PHE125A-TPO Leaflet

Page of 1
  Recoveries based on 83% thermal efficiency.  ASHRAE 90.1 compliant for efficiency and standby loss. 
   "J" dimension is for the burner housing only.  
 
Dimensions are in inches unless otherwise specified. 
 
For standard and optional equipment, see form PV 6006.  
 
Model 
Number 
Recovery gph   
Input 
Btu/h 
Dimensions 
(inches) 
Blower  
Motor 
Shipping 
Weight 
lbs  
40°- 120°F  40°- 140°F 
J   
HP 
Volt/Ph/Amps 
250 PHE 125A-TPO 
250 
200 
199,000 
24 
17 
1/3 
115/1
∅/8 
970 
500 PHE 125A-TPO 
500 
400 
399,000 
24 
17 
1/2 
115/1
∅/10 
990 
750 PHE 125A-TPO 
750 
600 
600,000 
27 
17 
1/2 
115/1
∅/10 
1070 
1000 PHE 125A-TPO 
1000 
800 
800,000 
27 
17 
1/2 
115/1
∅/10 
1110 
1250 PHE 125A-TPO 
1250 
1000 
1,000,000 
27 
17 
1/2 
115/1
∅/10 
1350 
1500 PHE 125A-TPO 
1500 
1200 
1,200,000 
27 
17 
1/2 
115/1
∅/10 
1360 
Gph 
#2 Oil 
1.4 
2.8 
4.3 
5.7 
7.2 
8.6 
TURBOPOWER
®
  OIL 
 
PACKAGED WATER HEATER 
POLYSHIELD
® 
POLYMER-LINED STORAGE TANK 
TANK SERIES 125 GALLONS HORIZONTAL 
PV 5458  04/05 
PVI INDUSTRIES, LLC 
FORT WORTH, TEXAS 76111 
(800) 784-8326 
 
(817) 335-9531 
 
www.pvi.com 
Product is patented in the U.S., Canada, and Mexico. 
VENTING REQUIREMENTS 
-.02" TO -.06" W.C. (NEGATIVE PRESSURE) 
 
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED 
UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.  
FOR PROPER SIZING, CONSULT VENTING SUPPLIER. 
STANDARD ELECTRICAL REQUIREMENTS 
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS. 
  MOTOR VOLTAGE:  
  208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL 
  REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR 
  AN OPTIONAL CONTROL CIRCUIT TRANSFORMER. 
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN 
AND SPECIFICATION WITHOUT NOTICE.