York TCHD18 THRU 60 User Manual

Page of 28
556454-YTG-A-0210
2
Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change without notice.
Certified dimensions will be provided upon request.
.
Physical and Electrical Data
MODEL
TCHD18
S41S3
TCHD24
S41S3
TCHD30
S41S3
TCHD36
S41S3
TCHD48
S41S3
TCHD60
S41S3
Unit Supply Voltage
208-230V, 1
 60Hz
Normal Voltage Range 
1
187 to 252
Minimum 
Circuit 
Ampacity
11.8 17.4 17.5 23.1 27.1 34.3 
Max. Overcurrent Device Amps 
2
20 30 30 40 45 60 
Min. Overcurrent Device Amps 
3
15 20 20 25 30 35 
Multi-Stage 
Compressor
No No No No No No 
Compressor 
Type 
Scroll Scroll Scroll Scroll Scroll Scroll 
Compressor Amps
Rated 
Load
9.0  13.5 12.8 17.3 20.5 26.3 
Locked 
Rotor
48.0 58.3 64.0 96.7 115.0 
134.0 
Crankcase 
Heater
Yes Yes Yes Yes Yes Yes 
Fan Diameter Inches
17.5 
17.5 
23 
23 
23 
23 
Fan Motor
Rated 
HP
1/8 1/8 1/4 1/4 1/4 1/4 
Rated 
Load 
Amps
0.60 0.60 1.45 1.45 1.45 1.45 
Nominal 
RPM
840 840 850 850 850 850 
Coil
Face Area Sq. Ft.
5.76 
5.76 
11.96 
11.96 
13.96 
13.96 
Rows 
Deep
1 1 1 1 1 1 
Fins 
Inches
23 23 23 23 23 23 
Refrigerant Lines
4
Max. Length
200
200
200
200
200
200
Max. Lift
65
65
65
65
65
65
Max. Drop
150
150
150
150
150
150
Liquid Line Set OD (Field Installed)
3 / 8 
3 / 8 
3 / 8 
3 / 8 
3 / 8 
3 / 8 
Vapor Line Set OD (Field Installed)
3 / 4 
3 / 4 
3 / 4 
3 / 4 
7 / 8 
7 / 8 
Unit Charge (Lbs. - Oz.) 
5
2 - 14 
3 - 5 
4 - 0 
4 - 8 
5 - 5 
5 - 6 
Charge 
Per 
Foot, 
Oz.
0.68 0.68 0.68 0.68 0.70 0.70 
Operating 
Weight 
Lbs.
130 135 195 215 240 250 
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. When more than 50 feet of interconnecting tubing and more than 30 feet of vertical lift is used, consult the Application Data (part number 
247077). For long-line applications, interconnecting lines over 100 feet must be installed with liquid line solenoid.
5. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add 
or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
B
C
A
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Including Fan Guard.
B
C
Liquid
Vapor
18
25-1/8
14-5/8
37
3/8”
3/4”
24
25-1/8
14-5/8
37
30
37-1/8
17-1/8
44-5/8
36
37-1/8
17-1/8
44-5/8
48
43-1/8
17-1/8
44-5/8
7/8”
60
43-1/8
17-1/8
44-5/8