York THGD18 THRU 60 User Manual

Page of 30
Subject to change without notice. Printed in U.S.A.
397763-YTG-B-0508
Copyright © 2008 by Johnson Controls, Inc. All rights reserved. 
Supersedes: 397763-YTG-A-0408
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
THGD60S41S1
EVAPORATOR COIL MODEL NO
FC/MC62
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1600
1800
2000
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
65.7 4.7  4.1 66.7 4.6  4.2 67.6 4.6  4.3 
70
64.7 5.1  3.7 65.4 5.0  3.8 66.1 4.9  3.9 
80
63.8 5.5  3.4 64.1 5.4  3.5 64.5 5.3  3.6 
47
60
56.9 4.4  3.8 57.4 4.4  3.9 58.0 4.3  4.0 
70
55.8 4.8  3.4 56.3 4.8  3.5 56.8 4.7  3.5 
80
54.7 5.2  3.1 55.2 5.2  3.1 55.6 5.1  3.2 
40
60
51.9 4.3  3.5 51.7 4.3  3.5 51.4 4.3  3.5 
70
50.6 4.8  3.1 51.1 4.7  3.2 51.7 4.7  3.2 
80
49.3 5.2  2.8 50.6 5.1  2.9 51.9 5.0  3.0 
30
60
44.1 5.0  2.6 43.6 5.0  2.5 43.1 5.0  2.5 
70
45.3 4.6  2.9 44.8 4.6  2.9 44.4 4.6  2.8 
80
46.5 4.2  3.2 46.1 4.2  3.2 45.6 4.1  3.2 
17
60
36.6 5.0  2.2 36.8 4.9  2.2 36.9 4.9  2.2 
70
36.0 4.5  2.4 36.5 4.5  2.4 37.1 4.4  2.4 
80
35.3 4.0  2.6 36.3 4.0  2.6 37.3 4.0  2.7 
10
60
27.3 4.7  1.7 27.7 4.6  1.7 28.1 4.6  1.8 
70
30.4 4.4  2.0 31.2 4.3  2.1 32.0 4.3  2.2 
80
33.4 4.0  2.4 34.7 4.0  2.5 35.9 4.0  2.7 
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MA20D 
MC62D 
1.00 1.00 1.00 
MV20D 
MC62D 
0.99 0.99 1.00 
Variable Speed 
Furnace
Coil
MBH
KW
COP
PV8*C20
MC62C 
1.00 1.00 1.00 
P(C,V)9*C20
MC62C 
0.99 0.97 1.03 
P(C,V)9*D20
MC62D 
0.99 0.96 1.03