Thermo Products OPB (24 User Manual

Page of 91
All installations and services must be performed by qualified service personnel. 
 
8.  As a final step in the installation, the appliance must be adjusted to deliver a 
temperature rise within the range of 50° to 80°F. Adjust the blower motor 
speed to obtain a temperature rise within the acceptable range. The required 
blower speed will depend on the airflow resistance of a supply and return air 
duct systems. 
 
I. Air 
Filters 
 
1. Filter Installation 
 
This OPB unit has been factory supplied with a high quality, re-usable filter 
rated for air velocities up to 600 ft/min.  
 
2.  Use of non-Thermo Pride Filters or Retention Means 
 
:  Failure to comply with minimum filter installation 
requirements may affect the performance and/or void the warranty on 
this unit.
 
 
If a method other than Thermo Pride filter racks is selected for retention of the 
filter and/or use of a different filter type is desired, refer to Table 4 for 
minimum sizing guidelines for selecting filter for the unit.  
 
Table 4: Minimum Required Filter Area (in square inches) 
 
Model Number 
 
Filter Type 
Maximum 
Air Velocity 
(ft/min) 
OPB24 OPB30  OPB36 
*Thermo Products 
Supplied 
Permanent 
 
600 
192 
 
240 
 
288 
 
Standard 
Permanent 
500 230 
288 
346 
Disposable 
300 
384 
480 
576 
 
∗  The Thermo Products supplied filter can be cut to size to fit other filter 
retention systems as long as the minimum size requirement is met.  
 
 NOTICE: Any internal stiffeners used in the filter must not be removed, 
although they can be cut to size as needed. 
 
23