York SVY48 THRU 60 User Manual

Page of 10
Johnson Controls Unitary Products
5
256819-YTG-J-1208
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow
80%
90%
Rated CFM
110%
120%
Capacity Factor
0.96
0.98
1.00
1.02
1.03
PHYSICAL & ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models 
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Blower - Diameter x Width
10 x 7
10 x 7
10 x 10
10 x 10
Motor
HP
1/3
1/2
3/4
1
Nominal RPM
1200
1200
1200
1200
Voltage
230
Amps
Full Load (230)
2.8
4.3
5.5
7.0
Filter
1
Type
DISPOSABLE OR PERMANENT
Size
16 x 20 x1
20 x 20 x1
22 x 20 x1
22 x 20 x1
Permanent Type Kit
1PF0601BK
1PF0602BK
1PF0603BK
1PF0603BK
Shipping / Operating Weight (lbs.)
140/134
170/164
AV - 196/185
SV - 194/181
AV - 199/188
SV - 195/184
1.Field supplied.
ELECTRICAL DATA - COOLING ONLY (60 Hz)
Models
Total Motor Amps
Minimum Circuit Ampacity
Max. O.C.P. 
Amps/Type
1
Minimum Wire 
Size A.W.G.
60 Hertz
60 Hertz
208V
230V
208V
230V
AVY24B**H21
3.2
2.8
4.0
3.5
15
14
AVY36C**H21
4.7
4.3
5.9
5.4
15
14
AVY48D**H21
6.1
5.0
7.6
6.9
15
14
SVY48D**N21
6.1
5.0
7.6
6.9
15
14
AVY60D**H21
7.8
7.0
9.7
8.8
15
14
SVY60D**N21
7.8
7.0
9.7
8.8
15
14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.