2100D and 2100TD Photoelectronic 
Smoke Detectors
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
A Division of Pittway
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing 
Please  thoroughly  read  System  Sensor  manual  I56-407, 
Guide  for  Proper  Use  of  System  Smoke  Detectors,  which 
provides  detailed  information  on  detector  spacing,  place-
ment,  zoning,  wiring,  and  special  applications.  Copies  of 
this manual are available at no charge from System Sensor. 
NOTICE: This manual should be left with the owner/user 
of this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
General Description
Model  2100D  is  a  2-wire  photoelectronic  smoke  detector 
that  uses  a  state-of-the-art  optical  sensing  chamber.  This 
detector  is  designed  to  provide  open  area  protection  and 
to  be  used  with  compatible  UL-listed  panels  only.  Model 
2100TD  features  a  restorable,  built-in,  fixed-temperature 
(135°F) thermal detector.
Specifications
Diameter:                                               5.5 inches (140 mm)
Height (including mounting bracket):      1.7 inches (43 mm)
Weight:                                                  5.3 oz. (150 g)
Operating Temperature Range:                Model 2100D:  32° to 120°F (0° to 50°C)
                                                             Model 2100TD:  32° to 100°F (0° to 39°C)
Operating Humidity Range:                     10% to 93% Relative Humidity, Noncondensing
Latching Alarm:                                     Reset by momentary power interruption
Heat Sensor (Model 2100TD only):          135°F Fixed Temperature Electronic Thermistor
Electrical Ratings
System Voltage –                                    Nominal: 
12 or 24 VDC
                                                             Minimum: 
8.5 VDC
                                                             Maximum: 
35 VDC
Maximum Ripple Voltage:                       30% of nom. Voltage (peak to peak)
Start-up Capacitance:                              0.02 µF maximum
Standby Current:                                    50 µA maximum
Alarm Ratings:                                       4.2 VDC minimum at 10 mA.
                                                             6.6 VDC maximum at 100 mA.
                                                             (Alarm current must be limited to 100 mA maximum by the control panel. If 
used, the RA400Z Remote Annunciator operates within the specified detector 
alarm currents.)
Reset Voltage:                                         2.5 VDC minimum
Reset Time:                                            0.3 seconds maximum
Start-up Time:                                        30 seconds maximum (after 60 second reset)
Installation of these detectors is simplified by the use of a 
mounting bracket and a plug-in screw terminal block that 
can be prewired to the system, allowing the detector to be 
easily  installed  or  removed  for  cleaning.  The  detector’s 
sensitivity can be tested in place using the MOD400R Test 
Module.  An  LED  on  the  detector  provides  a  local  visual 
indication  of  the  detector’s  status.  If  power  is  applied  to 
the detector, and it is functioning normally in standby, the 
status LED blinks every ten seconds. The LED also latches 
on in alarm.
Models 2100D and 2100TD feature a visual indication that 
maintenance is required – if the sensing chamber drifts out 
of its sensitivity limits, the LED ceases to blink.
The detectors also include an output that allows an optional 
Model RA400Z Remote Annunciator to be connected.