VI  Refrigerant Circuit ] 
- 91 -
HWE09120
GB
2. Indoor 
Unit
Part 
Name 
Symbol 
(functions) 
Notes Usage 
Specification Check 
method 
Linear 
expan-
sion valve
LEV
1)   Adjusts superheat at the 
indoor heat exchanger 
outlet during cooling
2)   Adjusts subcool at the 
heat exchanger outlet of 
the indoor unit during 
cooling
DC12V
Opening of stepping motor
driving valve 0-(1400) puls-
es
Refer to the section 
"Continuity Test with a 
Tester". 
Continuity between 
white, red, and or-
ange.
Continuity between 
yellow, brown, and 
blue.
Thermis-
tor
TH1 
(Suction air 
temperature)
Indoor unit control (Thermo)
     0°C [32°F]:15kohm
  10°C [50°F] :9.7kohm
  20°C [68°F]:6.4kohm
  25°C [77°F] :5.3kohm
  30°C [86°F] :4.3kohm
  40°C [104°F] :3.1kohm
Resistance check
TH2 
(Pipe temper-
ature)
1)   Indoor unit control (Frost 
prevention, Hot adjust)
2)   LEV control during heat-
ing operation (subcool 
detection).
TH3 
(Gas pipe 
temperature)
LEV control during cooling op-
eration (superheat detection)
TH4 
Outdoor air 
temperature)
Indoor unit control (Thermo)
Temperature 
sensor (In-
door air tem-
perature)
Indoor unit control (Thermo)
Yellow 
White 
Red 
Orange 
Brown Blue
M
1
273+t
R
0
=15k 
R
0/80
=3460
Rt =
15exp{3460(         -        )}
1
273