VII  Control ] 
- 115 -
HWE09120
GB
[3] Operation Flow Chart
1. Mode 
determination flowchart 
(1) Indoor unit (cooling, heating, dry, fan mode)
*Note 1. Indoor unit LEV fully closed : Opening 41.
*Note 2. The system may go into the error mode on either the indoor unit or the outdoor unit side. If some of the indoor units are 
              experiencing a problem (except water leakage), only those indoor units that are experiencing the problems will stop. 
              If the outdoor unit is experiencing a problem, all connected indoor units will stop.
*Note 3. The operation will be prohibited  when the set cooling/heating mode is different from that of the outdoor unit.
 Start
Remote controller 
display lit off
 Error mode
 Error stop
 Error display
Self-holding of 
protection function
Error command 
to outdoor unit
Indoor unit LEV 
fully closed.
Refer to 2-(1)
 Cooling operation.
Refer to 2-(2)
 Heating operation.
Refer to 2-(3) 
for dry operation.
Prohibition
Prohibition
Prohibition
 Dry display
 Heating display
Cooling display
 Dry mode
 Heating mode
 Fan mode
 Fan display
 Fan operations
 Operation mode
 Cooling mode
 Operation command to outdoor unit (to  2 )
Prohibition
"Blinking display on 
the remote controller"
FAN stop
 Breaker 
turned on
 Operation SW 
turned on
Auxiliary heater
ON
 Drain pump
ON
 3-minute 
drain pump ON
NO
NO
NO
NO
NO
NO
NO
NO
*Note 1
*Note 2
*Note 1
*Note 3
*Note 3
*Note 3
1. Protection function 
    self-holding cancelled.
2. Indoor unit LEV fully closed.
1. Auxiliary heater OFF
2. Low fan speed for
    1 minute
YES
YES
YES
YES
YES
YES
YES
YES
Normal operation
Error
Unit in the stopped state
 From outdoor unit
1