Mitsubishi P240 User Manual

Page of 334
VIII  Test Run Mode ] 
- 147 -
HWE09120
GB
3. 3-unit 
combination
(1) Cooling operation
Operation
Outdoor unit model
PUHY-P312TSJMU-A
PUHY-
P72TJMU-A
PUHY-
P120TJMU-A
PUHY-
P120TJMU-A
Operating 
conditions
Ambient 
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor 
unit
No. of connected 
units
Unit
6
No. of units in opera-
tion
6
Model
-
48/48/48/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
34 [75]
Outdoor 
unit
Electric current
A
72.0
Voltage
V
230
Compressor frequency
Hz
52
74
74
LEV open-
ing
Indoor unit
Pulse
387/387/387/310/310/310
SC (LEV1) 
141
185
185
LEV2
2100
2100
2100
Pressure
High pressure (after O/S)/low 
pressure (before accumulator)
MPa
[psi]
2.81/0.92
2.81/0.92
2.81/0.92
[408/134]
[408/134]
[408/134]
Temp. of 
each sec-
tion
Outdoor 
unit
Discharge (TH4)
°C [°F]
69 [156]
73 [163]
73 [163]
Heat exchanger out-
let (TH3)
44 [111]
40 [104]
40 [104]
Accumulator inlet
10 [50]
10 [50]
10 [50]
Accumulator outlet
10 [50]
10 [50]
10 [50]
SCC outlet (TH6)
24 [75]
20 [68]
20 [68]
Compressor inlet
17 [63]
15 [59]
15 [59]
Compressor shell 
bottom
47 [117]
42 [108]
42 [108]
Indoor 
unit
LEV inlet
20 [68]
20 [68]
20 [68]
Heat exchanger  
outlet
10 [50]
10 [50]
10 [50]