IX  Troubleshooting ]
- 226 -
HWE09120
GB
In the case of MA remote controller
3. Phenomena
"HO" or "PLEASE WAIT" display on the remote controller does not disappear, and no operation is performed even if the button 
is pressed. ("HO" or "PLEASE WAIT" display will normally turn off 5 minutes later after the power on.)
(1) Cause
1)   The power for the M-NET transmission line is not supplied from the outdoor unit.
2)   Short-circuited transmission line
3)   Incorrect wiring of the M-NET transmission line on the outdoor unit.
ŒDisconnected wire for the MA remote controller or disconnected line to the terminal block.
ŒThe indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
ŒThe male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector 
(CN40).
In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect-
ed to the female power supply switch connector (CN40) on the outdoor unit
4)   Disconnected M-NET transmission line on the indoor unit.
5)   Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or 
disconnected connector.
6)   Incorrect wiring for the MA remote controller
ŒShort-circuited wire for the MA remote controller
ŒDisconnected wire for the MA remote controller (No.2) and disconnected line to the terminal block.
ŒReversed daisy-chain connection between groups
ŒIncorrect wiring for the MA remote controller to the terminal block for transmission line connection (TB5) on the indoor unit
ŒThe M-NET transmission line is connected incorrectly to the terminal block (TB13) for the MA remote controller.
7)   The sub/main setting of the MA remote controller is set to sub.
8)   2 or more main MA remote controllers are connected.
9)   Indoor unit board failure (MA remote controller communication circuit)
10)  Remote controller failure
11)  Outdoor unit failure (Refer to IX [7] Troubleshooting Using the Outdoor Unit LED Error Display.)(page 278)
(2)  Check method and remedy
1)   When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
Refer to section IX [4] -7- (2) Troubleshooting transmission power circuit of outdoor unit for how to check the first item in the 
flowchart above.(page 270)(page 273)
YES 
YES 
YES 
NO 
NO 
YES 
YES 
NO 
NO 
NO 
Check the self-diagnosis LED 
Error found? 
Error found? 
Replace the ME remote 
controller with the MA 
remote controller
Check for 5 and 6. 
 
17  - 30V? 
 
Same symptom for all units in a  
system with one outdoor unit? 
Check  (1). 
Check  
2 and 3. 
Check 4. 
Correct  
the error. 
Correct  
the error. 
Measure voltages of the  
terminal block for transmission  
line (TB5) on the indoor unit. 
Is the error code 7102 
displayed? 
Indoor unit board or  
MA remote controller failure