IX  Troubleshooting ] 
- 229 -
HWE09120
GB
In case of ME remote controller
2. Phenomena
When the remote controller operation SW is turned on, a temporary operation display is indicated, and the display lights out 
immediately.
(1) Cause
1)   The power is not supplied to the indoor unit.
ŒThe main power of the indoor unit (AC208/230V) is not on.
ŒThe connector on the indoor unit board has come off.
ŒThe fuse on the indoor unit board has melted.
ŒTransformer failure and disconnected wire of the indoor unit
ŒThe indoor unit board failure
2)   The outdoor control board failure
As the indoor unit does not interact with the outdoor unit, the outdoor unit model cannot be recognized.
(2)  Check method and remedy
YES 
YES 
YES 
YES 
YES 
NO 
NO 
NO 
NO 
NO 
NO 
YES 
*1 
*1 
Check LED1 on the  
indoor unit control board. 
Is it lit? 
When it is lit 
When it is off  
or cannot be checked 
Check for the change of LED  
display by operating dip  
switch SW1 for self-diagnosis. 
Check voltage of the power supply  
terminal on the indoor unit. 
AC208/230V?
Check the fuse on  
the circuit board. 
Melted? 
Check 200V circuit for  
short circuit and ground fault 
Check the connection  
of the connector. 
Check the main power of  
the power supply wire 
Turn on the  
power again. 
Connector contact failure 
Disconnected? 
Check the resistance value  
of the transformer 
Within specification? 
Check the cause of the  
disconnected transformer. 
 Ground fault on the circuit board 
 Ground fault of the sensor and the LEV 
Check self-diagnosis function  
of outdoor unit 
Changed? 
Changed? 
Outdoor unit board failure 
Check self-diagnosis function of  
outdoor unit after the power on. 
Accidental  
error 
Indoor unit control  
board failure 
Correct  
the error. 
*1. Refer to the parts catalog “transformer check”.