Mitsubishi P240 User Manual

Page of 334
- 28 -
II  Restrictions ]
GB
HWE09120
[5] An Example of a System to which an MA Remote Controller is connected
1.  System with one outdoor unit (automatic address setup for both indoor and outdoor units)
(1) Sample control wiring
(2) Cautions
1)   ME remote controller and MA remote controller cannot 
both be connected to the same group of indoor units.
2)   No more than 2 MA remote controllers can be connected 
to a group of indoor units.
3)   A transmission booster is required in a system to which 
more than 32 indoor units (26 units if one or more indoor 
units of the 72 model or above is connected) are con-
nected.
4)   Automatic address setup is not available if start-stop in-
put (CN32, CN51, CN41) is used for a group operation of 
indoor units. Refer to "[5] 2. Manual address setup for 
both indoor and outdoor units".(page 30)
5)   To connect more than 2 LOSSNAY units to indoor units 
in the same system, refer to "[5] 2. An example of a sys-
tem with one outdoor unit to which 2 or more LOSSNAY 
units are connected".(page 30)
(3)  Maximum allowable length
1)   Indoor/outdoor transmission line
Maximum distance (1.25mm
2
 [AWG16] or larger)
L1 +L2+L3+L4
200m[656ft]
L1 +L2+L11+L12+L13
200m[656ft]
2)   Transmission line for centralized control
No connection is required.
3)   MA remote controller wiring
Maximum overall line length 
(0.3 to 1.25mm
2
 [AWG22 to 16])
m1
200m [656ft]
m2+m3
200m [656ft]
m4+m5
200m [656ft]
IC 
TB5 
TB15 
1 2 
00 
IC 
TB5 
TB15 
1 2 
00 
A B 
MA 
A B 
MA 
A B 
RC 
LC 
TB5 
00 
IC 
TB5 
M1 M2 M1 
M2 M1 
M2 
M1 M2 
M1 M2 
M1 M2 
1 2 
TB15 
IC 
TB5 
TB15 
1 2 
00 
00 
IC 
TB5 
TB15 
1 2 
00 
A B 
MA 
A B 
MA 
A B 
MA 
A B 
MA 
m1 
L1
m2 
L3 L4 
L12 L13 
m3 
m5 
m4 
Interlock operation with 
the ventilation unit 
TB3 
00 
00 
TB7 
TB3 
00 
TB7 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
TB3 
TB7 
OC 
OS1 
OS2 
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Leave the male
connector on
CN41 as it is.
SW2-1 OFF
Group Group 
Group 
Group 
L2 
L1