Mitsubishi Electronics PURY-P192YSKMU-A User Manual

Page of 4
Job Name:
Schedule Reference:
Date:
Specifications are subject to change without notice. 
© 2014 Mitsubishi Electric US, Inc.
Specifications
System
Module 1
Module 2
Unit Type
PURY-P192YSKMU-A (-BS)
PURY-P96YKMU-A (-BS)
PURY-P96YKMU-A (-BS)
Nominal Cooling Capacity (460V)
Btu/h
192,000
96,000
96,000
Nominal Heating Capacity (460V)
Btu/h
215,000
108,000
108,000
Operating Temperature Range *1
Cooling (Outdoor) *2
Refer to Module Data
23~115° F (-5~46° C) DB 
Heating (Outdoor)
 -4~60° F (-20~15.5° C) WB
External Dimensions (H x W x D)
In.
mm
Refer to Module Data
64-31/32 x 48-1/16 x 29-5/32 
1,650 x 1,220 x 740
64-31/32 x 48-1/16 x 29-5/32 
1,650 x 1,220 x 740
Net Weight
Lbs. / kg
1,148 (520)
574 (260)
574 (260)
External Finish
Refer to Module Data
Pre-coated galvanized steel sheet
Electrical Power Requirements
Voltage, Phase, Hertz
Refer to Module Data**
460V, 3-Phase, 60Hz
Minimum Circuit Ampacity (MCA)
A
Refer to Module Data**
15
15
Maximum Fuse Size
A
Refer to Module Data**
20
20
Piping Diameter
From Twinning Kit to Indoor Units                                  
(Brazed) (In. / mm)
Liquid (High Pressure)
7/8 (22.2) Brazed
Refer to System Data
Gas (Low Pressure)
1-1/8 (28.58) Brazed
Max. Total Refrigerant Line Length
Ft.
2,461
Refer to System Data
Max. Refrigerant Line Length                 
(Between ODU & IDU)
Ft.
541
Max. Control Wiring Length
Ft.
1,650
Indoor Unit
Total Capacity
50~150% of ODUs
Refer to System Data
Model / Quantity
P06~P96/1~48
Refer to System Data
Sound Pressure Level
dB(A)
61
Refer to System Data
Fan
Type x Quantity
Refer to Module Data
Propeller fan x 1
Propeller fan x 1
Airflow Rate
CFM
6,200
6,200
External Static Pressure
In. WG (Pa)
Refer to Module Data
Selectable; 0, 0.12 or 0.24”WG; factory set to 0”W.G.
Compressor Operating Range
8% to 100%
Refer to System Data
Compressor Type x Quantity
Refer to Module Data
Inverter-driven Scroll  
Hermetic x 1
Inverter-driven Scroll  
Hermetic x 1
Refrigerant
Refer to Module Data
R410A x 26 lbs + 1 oz   
(11.8 kg)
R410A x 26 lbs + 1 oz   
(11.8 kg)
Protection Devices
High Pressure
Refer to Module Data
High pressure sensor, High 
pressure switch at 4.15 MPa 
(601 psi)
High pressure sensor, High 
pressure switch at 4.15 MPa 
(601 psi)
Inverter Circuit  
(Comp. / Fan)
Over-current protection
Over-current protection
Fan Motor
Thermal switch
Thermal switch
AHRI Ratings
(Ducted/Non-Ducted)
EER
11.6 / 11.9
Refer to System Data
IEER
19.3 / 18.2
COP
3.64 / 3.47
Simultaneous Rating
(Ducted/Non-Ducted)
SCHE *3
17.40 / 21.81
Refer to System Data
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants
Standard: ≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
Sea Coast (BS): ≥1μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.
Outdoor Unit:
 16-TON PURY-P192YSKMU-A (-BS)
(Consists of Two PURY-P96YKMU-A (-BS) and One CMY-R100CBK2 Twinning Kit)
UNIT OPTION
 
□ Standard Model……..….........…...………….PURY-P192YSKMU-A 
 
□ Sea Coast (BS) Model………....……….PURY-P192YSKMU-A-BS
OUTDOOR VRF HEAT PUMP WITH HEAT RECOVERY 
SYSTEM FEATURES
•  INVERTER-driven compressor
•  Air-source, simultaneous cooling and heating
•  Long line lengths - for details see Engineering Manual
•  Connects to CITY MULTI indoor units
•  Controlled via CITY MULTI Controls Network
NOTES:
*1. Harsh weather environments may demand performance enhancing equipment.  
     Ask your Mitsubishi Electric representative for more details about your region.
*2. For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit  Submittal.
 
*3. Simultaneous Cooling and Heating Efficiency
**  Each individual module requires a separate electrical connection.  
  Refer to electrical data for each individual module.
OPTIONAL PARTS
 
□ Twinning Kit (required)..............................................…CMY-R100CBK2
 
□ Joint Kit.............................…for details see Pipe Accesories Submittal
 
□ Joint Adapter Kit................…for details see Pipe Accesories Submittal
 
□ Low Ambient Kit ...............…..for details see Low Ambient Kit Submittal
 
□ Snow/Hail Guards Kit......…for details see Snow/Hail Guards Kit Submittal