Warning: As a safety precaution, install a circuit breaker with a 
minimum value of 15 Amps between the equipment and the DC 
power source. 
Always connect the wires to the LAN equipment first before you 
connect the wires to the circuit breaker. Do not work with HOT 
feeds to avoid the danger of physical injury from electrical shock. 
Always be sure that the circuit breaker is in the OFF position 
before connecting the wires to the breaker.
 E9
Warning: Do not strip more than the recommended amount of 
wire. Stripping more than the recommended amount can create 
a safety hazard by leaving exposed wire on the terminal block 
after installation. 
 E10
Warning: When installing this equipment, always ensure that the 
frame ground connection is installed first and disconnected last. 
 E11
Warning: Check to see if there are any exposed copper strands 
coming from the installed wire. When this installation is done 
correctly there should be no exposed copper wire strands 
extending from the terminal block. Any exposed wiring can 
conduct harmful levels of electricity to persons touching the 
wires. 
 E12
This system works with positive grounded or negative grounded 
DC systems. 
 E13
Circuit Overloading: Consideration should be given to the 
connection of the equipment to the supply circuit and the effect 
that overloading of circuits might have on overcurrent protection 
and supply wiring. Appropriate consideration of equipment 
nameplate ratings should be used when addressing this 
concern. 
 E21