VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. 
When  ventilating  to  an  adjoining  unconfined  space,  you  must 
provide two permanent openings: one within 12" of the ceiling 
and one within 12" of the floor on the wall connecting the two 
spaces (see options 1 and 2, Figure 5). You can also remove door 
into adjoining room (see option 3, Figure 5). Each ventilation grill 
or opening shall have a minimum free area of one square inch per 
1,000 BTU/HR of the total input rating of the gas equipment in 
the confined space.
Figure 5
WARNING:  Rework worksheet, adding the space of the 
adjoining unconfined space. The combined spaces must have 
enough fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must 
provide two permanent openings: one within 12" of the ceiling 
and one with 12" of the floor. Connect these items directly to the 
outdoors  or  spaces  open  to  the  outdoors. These  spaces  include 
attics and crawl spaces. In most cases for direct communication 
with the outdoors or direct communication through a vertical duct 
a free area opening of one square inch per 4,000 BTU/HR of heater 
input rating for each grill. If a horizontal duct is used, a grill free 
area or duct opening shall have a free area opening of one square 
inch per 2,000 BTU/HR for each grill. Follow the National Fuel 
Code NFPA 54/ANSI Z223.1, Section 5.3 Air for Combustion and 
Ventilation for required size of ventilation grills or ducts.
IMPORTANT:  Do  not  provide openings  for  inlet or  outlet air 
into attic if attic has a thermostat-controlled power vent. Heated 
air entering the attic will activate the power vent.
Figure 6
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR