Monessen Hearth CDVR33N/PV7 User Manual

Page of 60
74D3000
15
BLDV7 Series Gas Fireplace
Vent InStaLLatIon 
w
arn
In
G
horizontal sections of this vent system require a minimum of 3" clearances 
to combustibles at the top of the flue and 1" clearance at the sides and 
bottom until the flue penetrates the outside wall. 
a minimum 1" clearance 
all around the flue is acceptable at this point of penetration.
If the vertical rise is 7
1
/
2
 ft. or more, only a 1" clearance is needed on top 
of any horizontal run.
Vertical sections of this vent system require a minimum of 1" clearance to 
combustibles on all sides of the pipe.
Figure 11 - 
Combustible 
Clearances for Vent 
Pipe 
12”
1”
1”
3”
FP2338
min. vent clear
A minimum of 3" clearance 
to the top is required along 
horizontal length until flue 
pipe  penetrates  outside 
wall. 
A minimum 1" clearance 
t o   c o m b u s t i b l e s 
permitted  all  around 
flue at outside wall
Vertical Rise Required 
Before Horizontal Run
FP338