Monessen Hearth CDVR33N/PV7 User Manual

Page of 60
74D3000
4
BLDV7 Series Gas Fireplace
MILLIVoLt - CheCK GaS preSSure and eLeCtrICaL InStaLLatIon 
1.  Check gas type. The gas supply must be the same as 
stated on the appliance’s rating decal. If the gas supply 
is different from the fireplace, Stop! Do not install the 
appliance. Contact your dealer immediately.
.  To ease installation, a 4" (610 mm) flex line with manual 
shut-off  valve  has  been  provided  with  on  this  appli-
ance. Install and attach 1/" gas line onto shut-off 
valve. 
3.  After completing gas line connection, purge air from 
gas line and test all gas joints from the gas meter 
to the fireplace for leaks. Use a solution of 50/50 
water and soap solution or a gas sniffer. 
4.  To adjust flame height, turn HI/LO knob to HI to get 
maximum pressure to burner. Turn HI/LO knob to 
LO to get minimum pressure. 
5.  To  check  gas  pressures  at  valve,  turn  captured 
screw counter clockwise  or 3 turns and then place 
tubing to pressure gauge over test point. Turn unit 
to high. Figure 32. After taking pressure reading, 
be sure and turn captured screw clockwise firmly 
to reseal. Do not over torque. Check test points for 
gas leaks.
eLeCtrICaL wIrInG
This fireplace will work without any electrical supply. Electricity is only needed to operate 
blower.
note: If installed in mobile home, fireplace must be bolted securely to floor. 
FP1979
Millivolt gas valve
FP1979
Figure 32 - 
Gas Pressure Check at Gas Valve 
Pressure 
Test “IN”
Pressure 
Test “OUT”
HI/LO Knob
Pilot Adjustment Screw 
w
arn
In
G
Do  not  use  open  flame  to  check  for  gas 
leaks.
w
arn
In
G
electrical connections should only be performed 
by a qualified, licensed electrician. Main power 
must be off when connecting to main electrical 
power supply or performing service. all wiring 
shall be in compliance with all local, city and 
state codes. the appliance, when installed, must 
be  electrically  grounded  in  accordance  with 
local codes or in the absence of local codes, 
with the national electrical Code anSI/nFpa 70 
(latest  edition)  and  Canadian  electrical  Code, 
CSa C22.1.
C
aut
Ion
Label  all  wires  before  disconnecting  when 
servicing  controls.  wiring  errors  can  cause 
improper and dangerous operation.
Verify proper operation after servicing.