Monessen Hearth CDVR33N/PV7 User Manual

Page of 60
74D3000
19
BLDV7 Series Gas Fireplace
Vent InStaLLatIon 
.  Remove soil to a depth of approximately 16” (406 mm) 
below base of snorkel. Install drain pipe. Install window 
well  (not  supplied).  Refill  hole  with  1”  (305  mm)  of 
coarse  gravel  leaving  a  clearance  of  approximately  4” 
(10 mm) below snorkel. Figure 21
3.  Install vent system.
4.  Ensure a watertight seal is made around the vent pipe 
coming through the wall.
5.  Apply  high  temperature  sealant  caulking  (supplied) 
around the 4” and 7” snorkel collars.
6.  Slide the snorkel into the vent pipes and secure to the 
wall.
7.  Level the soil so as to maintain a 4” (10 mm) clearance 
below snorkel. Figure 21
BG402a
Top Vent
Below grade installation
1/26/00   djt
Firestop
7” Pipe
7TDVSNORK 
(Snorkel)
4”  (10  mm) 
C l e a r a n c e 
Min.
Window 
Well
Gravel
Drain
BG40a
Figure 21 - 
Below Grade Installation
*A minimum of 4” (610 mm) verti-
cal  pipe  must  be  installed  when 
using the 7TDVSNORK Kit.
4” (610 mm) 
Minimum*
Screws
Foundation Wall
Do not back fill around snorkel.
a clearance of at least 4” must be maintained 
between the snorkel and the soil.
If  the  foundation  is  re-
cessed, 
use 
recess 
brackets  (not  supplied) 
for  securing  lower  por-
tion  of  the  snorkel.  Fas-
ten brackets to wall 
first, then secure 
to  snorkel  with 
self  drilling  #8  x 
1/  sheet  metal 
screws. It will be 
necessary to ex-
tend  vent  pipes 
out as far as the 
protruding  wall 
face. Figure 22
VertICaL throuGh-the-rooF appLICa-
tIon
his gas fireplace has been approved for:
  Vertical installations up to 40’ (1 m) in height. Up to 
a 10’ (3 m) horizontal vent run can be installed within 
the vent system using a maximum of two 90° elbows. 
Figure 23
  Up to two 45° elbows may be used within the horizontal 
run. For each 45° elbow used on the horizontal plane, 
the  maximum  horizontal  length  must  be  reduced  by 
18” (450 mm). 
example: Maximum horizontal length:
 
No elbows 
=  10’ (3 m)
 
1 x 45° elbow  =  8.5’ (.6 m)
 
 x 45° elbows  =  7’ (.1 m)
  A minimum of an 8’ (.5 m) vertical rise is required.
  Two sets of 45° elbow offsets may be used within the 
vertical sections. From 0 to a maximum of 8’ (.5 m) of 
vent pipe can be used between elbows. Figure 23
  7DVCS  supports  offsets.  Figure  27.  This  application 
will require that you first determine the roof pitch and 
use the appropriate starter kit. (Refer to Venting Com-
ponents List)
  The maximum angular variation allowed in the system 
is 70°. Figure 24
  For the minimum height of the vent above the highest 
point of penetration through the roof refer to Page 1, 
Figure 28.
Max. Height 40’ (12 m)
Min. Height 8’ (2 mm)
Max. 10’ (3 m)
12” (305 mm)
Min.
Support Straps 
Every 3' (914 mm)
FP1183
Figure 23 - 
Support Straps for Horizontal Runs
BG401
Snorkel
2/10/99   djt
Snorkel
Wall 
Screws
Foundation 
Recess
Watertight 
Seal Around 
PIpe
Sheet Metal 
Screws
BG401
Figure 22 - 
Snorkel Installation, 
Recessed Foundation