Monessen Hearth CDVR33N/PV7 User Manual

Page of 60
74D3000
9
BLDV7 Series Gas Fireplace
CLearanCeS
CLearanCeS to CoMBuStIBLeS 
ManteL CLearanCeS 
note: The  combustible  area  above  the  facing  must  not  protrude  more  than  3/4"  from  the 
facing. If it does, it is considered a mantel and must meet the mantel requirements listed in 
this manual.
Figure 4 - 
Clearances From The Mantel, Ceiling, and Side Wall
w
arn
In
G
Follow these instructions carefully to ensure safe installation. Failure 
to follow instructions exactly can create a fire hazard.
the  appliance  cannot  be  installed  on  a  carpet,  tile  or  other 
combustible material other than wood flooring. If installed on carpet 
or vinyl flooring, the appliance shall be installed on a metal, wood 
or noncombustible material panel extending full width and depth 
of the appliance.
note
All mantel shelves, regardless of depth, should be a minimum of 13" from 
top opening of fireplace. Mantel shelf shall not exceed 1" maximum depth 
at 13" minimum height from opening.
71” Minimum
Ceiling
13” Min.
From Opening
12” Max.
Depth
6”
Min.
FP2333
BLDV mantel clear
FP333
45°
1”
256O”
3”
5”
156O”
6”
356O”
456O”
FP2334a
BLDV side leg clear
Figure 4a - 
Mantel Clearances
Side of Fire-
place Opening
Wall
Combustible 
Material Area
FP334a
top View