Figure 35
A =   *Clearance above grade, veranda, porch, deck or balcony 
[*12 inches (30cm) minimum]
B =  clearance to window or door that may be opened [*12 inches 
(30cm) minimum for appliances < 100,000 Btuh (30kW)
C =  clearance  to  permanently  closed  window  [minimum  12 
inches (30cm) recommended to prevent condensation on 
window]
D =  vertical  clearance  to  ventilated  soffit  located  above  the 
terminal within a horizontal distance of 24 inches (60 cm) from 
the center of the terminal [18 Inches (46 cm) minimum
E  =  clearance  to  unventilated  soffit  [12  inches  30cm) 
minimum]
F  =  clearance to outside corner [See Page 21]
G =  clearance to inside corner [See Page 21]
H =  *not  to  be  installed  above  a  meter/regulator  assembly 
within 3 feet (90cm) horizontally from the center-line of 
the regulator
I  =  clearance to service regulator vent outlet [*6 feet (1.8m) 
minimum]
J  =  clearance to non-mechanical air supply inlet to building or 
the combustion air inlet to any other appliance [*12 inches 
(30cm) minimum for appliances ≤ 100,000 Btuh (30 kW)
 
  36 inches (90cm) minimum for appliances > 100,000 Btuh 
(30kW)]
K =  clearance to a mechanical air supply inlet [* 6 feet (1.8m) 
minimum]
L  =  †clearance above paved sidewalk or a paved driveway located 
on public property [*7 feet (2.1m) minimum]
M =  clearance under veranda, porch, deck, or balcony [*12 inches 
(30cm) minimum ¥]
†    a  vent  shall  not  terminate  directly  above  a  sidewalk  or 
paved driveway which is located between two single family 
dwellings and serves both dwellings*
¥    only permitted if veranda, porch, deck, or balcony, is fully 
open on a minimum of 2 sides beneath the floor*
*    as  specified  in  CGA  B149  Installations  Codes  or  ANSI 
Z223.1.  Note:  Local  Codes  or  Regulations  may  require 
different clearances.
VENT CLEARANCES