taBle 1. Branch cIrcuIt wIre sIZe.
These  ampacities  relate  only  to  conductors 
described  in  Table  310-13  of  the  NEC. 
For  ambient  temperatures  over  30°C,  see 
Correction Factors, Note 13 in the NEC.
electrIcal
General
Check the water heater model and rating plate information against 
the  characteristics  of  the  branch  circuit  electrical  supply.  Do  not 
connect the heater to an improper source of electricity. 
Voltage applied to the heater should not vary more than +5% to -10% 
of the model and rating plate marking for satisfactory operation.
Do 
not energize the branch circuit for any reason before the water 
heater tank is filled with water. Doing so may cause the heating 
elements to fail.
The factory wiring is attached to a terminal block on the unit. The 
branch circuit is connected to the block through an opening provided 
on the heater. Factory terminal block has 500 MCM maximum copper 
wire size capacity in each opening. If apparent field wire size is over 
500 MCM multiple terminal blocks will be furnished. If other opening 
sizes are desired they should be specified when unit is ordered.
The  installation  must  conform  to  these  instructions  and  the  local  
code authority having jurisdiction. Grounding and electrical wiring 
connected to the water heater must also conform to the National Electrical 
Code, NFPA 70. This publication is available from The National Fire  
Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
Branch cIrcuIt
The branch circuit wire size should be established through reference 
to the 
nec (national electrical code) or other locally approved 
sources in conjunction with the water heater amperage rating.. Wire 
rated at 75°C should be used. For convenience, portions of the wire 
size tables from the Code are reproduced in Table 1. It is suggested 
the electrician size the branch circuit at 125 percent of the heater 
rating and further increase wire size as necessary to compensate 
for voltage drop in long runs. Voltage drop should not exceed 3% 
at the water heater.
heater cIrcuIts
The water heater’s electrical components are pictured and identified 
by the Features and Components illustrations on pages 6 and 7. 
The model and rating plate illustration identifies the heater electrical 
characteristics. The heater has two electrical circuits:
Control Circuit: 120V circuit containing all safety and control devices.  
The control circuit operates the contactors in the power circuit.
Power Circuit: High voltage, single or three phase circuit that carries 
the heating element load.
The following section and pages describe the water heater circuits 
and includes wiring diagrams. 
control cIrcuIts
The heater is equipped with one of the following control circuits, 
resulting in:
A.  Thermostats (mechanical)... where all of the heating elements 
  are  switched  on/off  by  one  or  more  thermostats.  Heaters 
  with thermostat control are adjusted as described in TEMPERATURE 
  REGULATION section of this manual, see Page 14.
B.  Step controlled element operation...where elements are staged 
  on/off  individually  or  in  groups  rotationally  by  the  controller. 
  An optional feature is modulation which operates in conjunction with 
  the staged on/off element operation.
C.  Sequencer... operates in conjunction with a thermostat (mechanical). 
  The sequence is activated by a thermostat then the sequence 
  switches on the heater elements in 3 sequences (multiple elements 
  and contactors are required). 
 Additional instructional literature is provided with heaters equipped 
with modulating solid state step control or a sequencer.   
All control circuits are operated on single-phase 120 volt current.
Control circuit wiring is 14 Awg, AWM (Appliance Wiring Material) 
type, rated 600 volts, 105°C.
Standard equipment includes control circuit fusing.
power cIrcuIt
Power circuit wiring is type THHN (or equivalent) rated 600 volts, 
105°C, sized as necessary.
The following wiring diagrams are included in this manual to show 
typical arrangements of electrical components in the control and power 
circuits by voltage and phase characteristics. They are to be used as a 
reference by the installer or servicer in performing their work. An actual 
diagram of the water heater wiring is furnished with the heater.