3com 8807 Reference Guide

Page of 1099
890
C
HAPTER
 51: P
O
E PSU S
UPERVISION
 C
OMMANDS
Parameter
None
Description
Use the display poe-power alarm command to display detailed alarm 
information about the PoE PSUs.
Example
# Display detailed alarm information about the PoE PSUs.
<SW8800> display poe-power alarm
 
 PSU alarm detail, PSU number : 2
 
 PSU 1 alarm : NORMAL
 
 PSU 2 alarm : NOTLINK      Controller/Rectifier communication  Fail
/Rectifier not in present 
display poe-power 
dc-output state
Syntax
display poe-power dc-output state
View
Any view
Parameter
None
Description
Use the display poe-power dc-output state command to display the current 
DC output state of the PoE PSUs.
Example
# Display the current DC output state.
<SW8800> display poe-power dc-output state
 
DC Output State : Normal 
Table 121   Description on the fields of the display poe-power alarm command
Field 
Description 
NORMAL 
Normal 
NOTLINK 
The PSU is disconnected. That is, the controller was able to communicate with 
the PSU; but it cannot now. Power-cycling the unit or re-inserting a new PSU 
can resolve this problem. 
INERROR 
The PSU input is in trouble. Restoring the AC input can resolve this problem. 
OUTERROR 
The PSU output is in trouble, the PSU cannot output normal DC voltage. 
HIGHVOL 
The PSU is over-voltage. The PSU is shut down because the output voltage is 
too high. 
HIGHTEP 
It is overheated in the PSU. 
FANERROR 
The PSU fan is in trouble. 
CLOSE 
The PSU is shut down remotely. 
CURLIMIT 
The PSU is current limited.