Bunn cdbcf 15 User Guide

Page of 48
Page 17
FIG. 17-2  LEVEL PROBES
LEVEL PROBE SYSTEM
Location:
 
The level probes are located inside the tank lid.
Operation:
 
The level probes sense the water level in the tank 
by the conductive minerals in the water grounding 
out the very low AC voltage applied to the probes. The 
circuit monitors the time it takes the water to drop 
the distance from the short probe to the long probe. 
Proper "initial set up", and keeping mineral build up 
off the probes/grommets, is required for this system 
to operate properly. A brew abort feature is "built in". 
In the event that the drop in water level from the short 
probe to the long probe takes too long, the brew cycle 
will abort and return to the main screen. This could 
be caused by: Mineral build up on probes/grommets 
(very hard water); probes shorting to top cover (verify 
the mylar shield(s) are installed; plugged outlet (ie: 
sprayhead limed up); incorrect operator use with the 
pour over model (ie: pour in water and pressing "start" 
button)
Test Procedures:
1.    Enter programming level 2, scroll to "Refi ll". NOTE: 
This screen only reads the long probe (blue wire) and 
is used for setting the refi ll conductance threshold.
Alternate: Scroll to "Service Tools".
Then scroll to "LP1 & LP2". LP1 = short probe, LP2 
= long probe.
2.  A high reading (approximately 255) indicates water 
is not touching, or not conductive enough to ground 
the circuit. A low reading (0-2) indicates the probe is 
grounded.
Removal and Replacement:
1.  Disconnect the brewer from the power source and 
allow tank to cool.
2.  Remove nut, wire, and washers from probe.
3.  Pull probe straight up from grommet.
4.  When reinstalling, ensure long probe is connected 
to the blue wire, and short probe is connected to the 
brown wire. 
NOTE: Heavy mineral build up on probes could indicate 
that the tank, lid, and grommets may need to be de 
limed as well.
FIG. 17-1  LEVEL PROBES
39132 061809