APC 100KVA PDU w/ 480 PRI 208/120 SEC K 20 Rated XMER PD100G6FK20 User Manual

Product codes
PD100G6FK20
Page of 72
Section 2: Technical Specifications
SPDU Technical Handbook
27
PD300G6FK13
Input. 
Output. 
SPDU physical. 
Sidecar physical. 
Environmental. 
Nominal Input Voltage:
480V, 3PH
Input Frequency (Hz):
60 Hz, +/- 3 Hz
Transformer Type:
K13
Efficiency:
97%
Main Breaker Rating:
450A
Maximum Input Current:
361A
Load Capacity:
300 kVA
Nominal Output Voltage:
208V / 120V
Full Load Heat Output:
26854 BTU/hr
Impedance:
3.94%
Voltage Regulation:
3.44 @ .8 power factor, 1.62 @ 1.0 power factor
Transformer Taps:
2 @ 2.5% full capacity above nominal, 
4 @ 2.5% full capacity below nominal
Net Height:
81.5 inches (207.01 cm), 
includes removable 5.5-inch (13.97 cm) top box
Net Width:
45 inches (114.30 cm)
Net Depth:
38.5 inches (97.79 cm)
Net Weight:
2700 pounds (1224.70 kg)
Standard Color:
Black
Net Height:
81.5 inches (207.01 cm), 
includes removable 5.5-inch (13.97 cm) top box
Net Width:
20 inches (50.80 cm)
Net Depth:
38.5 inches (97.79 cm)
Net Weight:
590 pounds (267.62 kg)
Standard Color:
Black
Operating Environment:
0 - 40°C (32 - 104°F)
Operating Relative Humidity:
0 - 95%, non-condensing
Audible Noise:
55 decibels
Protection Class:
NEMA 1
UL Certification:
UL60950