APC InfraStruXure PD60G6FK1 User Manual

Product codes
PD60G6FK1
Page of 10
 
 
Page 2 
10/05/09 
 
1.4   SYSTEM 
DESCRIPTION 
 
SELECT OR INSERT APPLICABLE VALUE BELOW. 
 
A. 
Design Requirements:  The PDU shall be sized for [60 kVA] [150 kVA]. 
 
B. 
System Characteristics: 
1. 
Physical: 
a.  External width dimensions shall be 23.5 inches (597 mm) for 60 kVA PDU, and 
29.4 inches (747 mm) for 150 kW PDU. 
b.  External depth dimensions shall be 35.4 inches (900 mm). 
c.  The PDU shall have a maximum external height of 81.5 inches (2070 mm) to allow 
passage through a standard 7 foot (2134 mm) doorway without tipping. 
2. 
Input: 
a.  AC input nominal voltage shall be [208 volts] [480 volts] [600 volts], three-phase, 3 wires, 
60 hertz. 
 
150 kW IS AVAILABLE IN 480 VOLTS ONLY.  SELECT APPLICABLE VALUE ABOVE. 
 
b.  The PDU shall contain a [60 kVA] [150 kVA] NEMA TP-1 compliant, energy efficient, 
isolation transformer, which shall be rated for modern data center IT loads. 
c.  Maximum frequency range shall be 55 hertz to 65 hertz. 
3. 
PDU Output:  AC nominal output voltage; 208 volts, three-phase, 4 wires, 60 hertz. 
4. 
Output Distribution: 
a.  Distribution Panels:  The PDU shall contain two 42 position output distribution panels.  
Each panel shall have a nominal current rating of 225 amperes, and a withstand rating of 
22,000 AIC.  The distribution panels shall accommodate 1 pole, 2 pole, or 3 pole snap-in or 
bolt-in breakers, with current capacity ranging from 10 amperes to 150 amperes.  
20 ampere and 50 ampere breakers shall be used in conjunction with the below mentioned 
flexible distribution conducts and rack-mounted power distribution units to provide a 
pre-configured, tested, and UL 60950 listed branch distribution system. 
b.  Flexible Distribution Conductors:  For purposes of overhead distribution wiring of data 
center branch circuits, flexible conductors of either an SJO type, or TC type shall be 
available as a distribution means.  Flexible conductors shall be equipped with NEMA cord 
caps and shall be agency-approved under UL 60950. 
 
1.5   SUBMITTALS 
 
A. 
General:  See [Section 01 33 00 - SUBMITTAL PROCEDURES] [Section 01300 - SUBMITTALS]. 
 
B. 
Product Data:  Submit product data showing material proposed.  Submit sufficient information to 
determine compliance with the Drawings and Specifications.  Product data shall include, but shall 
not be limited to, the following: 
1. 
As bid system bill of materials. 
2. 
Product catalog sheets or equipment brochures. 
3. 
Product guide specifications. 
 
C. 
Shop Drawings:  Submit shop drawings for each product and accessory required.  Include 
information not fully detailed in manufacturer’s standard product data, including, but not limited to, 
the following: 
1. 
Installation information, including, but not limited to, weights and dimensions. 
2. 
Information about terminal locations for power and control connections. 
3. 
Drawings for requested optional accessories. 
 
D. 
Wiring Diagrams:  Submit wiring diagrams detailing power, signal, and control systems, clearly 
differentiating between manufacturer-installed wiring and field-installed wiring, and between 
components provided by the manufacturer and those provided by others.