KitchenAid 30" Retractable Downdraft System with Interior Blower Motor Use & Care Manual

Page of 44
8
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in 
conformance with National Electrical Code, ANSI/NFPA 70 (latest 
edition) or CSA Standards C22.1-94, Canadian Electrical Code, 
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes 
and ordinances.
If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrician determine that  
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association 
1 Batterymarch Park 
Quincy, MA 02169-7471
CSA International 
8501 East Pleasant Valley Road 
Cleveland, OH 44131-5575
 
A 120-volt, 60 Hz., AC-only, 15-amp, fused electrical  
circuit is required.
 
If the house has aluminum wiring, follow the procedure 
below:
1.  Connect a section of solid copper wire to the pigtail leads.
2.  Connect the aluminum wiring to the added section 
of copper wire using special connectors and/or tools 
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended 
procedure. Aluminum/copper connection must conform with 
local codes and industry accepted wiring practices.
 
Wire sizes and connections must conform with the rating of 
the appliance as specified on the model/serial/rating plate. 
The model/serial/rating plate is located on the front of the 
downdraft vent, above the wiring box cover.
 
Wire sizes must conform to the requirements of the National 
Electrical Code, ANSI/NFPA 70 (latest edition) or CSA 
Standards C22. 1-94, Canadian Electrical Code, Part 1  
and C22.2 No. 0-M91 (latest edition) and all local codes  
and ordinances.
Venting Requirements
IMPORTANT: Make sure there is proper clearance within the wall 
or floor before making exhaust vent cutouts.
 
Use heavy (rigid) metal vent.
 
Venting system must terminate to the outside.
 
Do not terminate the vent system in an attic or other 
enclosed area.
 
Do not use 4" (10.2 cm) laundry-type wall caps.
 
Do not install 2 elbows together.
 
Do not use plastic or metal foil vent.
 
The length of vent system and number of elbows should  
be kept to a minimum to provide efficient performance.
 
Use no more than three 90° elbows.
 
Make sure there is a minimum of 24" (61 cm) of straight vent 
between the elbows if more than one elbow is used.
 
Use clamps or duct tape to seal all joints in the vent system.
 
Use caulking tape to seal the exterior wall or floor opening 
around cap.
 
Do not cut joist or stud. If vent cutout falls over a joist  
or stud, a supporting frame must be constructed.
Flexible metal vent is not recommended. If it is used, calculate 
each foot of flexible vent as 2 ft (0.6 m) of rigid metal vent.
Flexible elbows count twice as much as standard elbows.
Recommended vent system length:
For either interior-mounted or exterior-mounted blower 
installations, the vent system length should not exceed the 
maximum lengths listed in the “Maximum Length of Vent 
System” chart. See “Calculating Vent System Length” in the 
“Venting Methods” section in the Installation Instructions.
Cold Weather Installations
An additional backdraft damper should be installed to minimize 
backward cold airflow and a thermal break should be installed 
to minimize conduction of outside temperatures as part of the 
vent system. The damper should be on the cold air side of the 
thermal break.
The break should be as close as possible to where the vent 
system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of makeup air systems 
when using ventilation systems greater than specified CFM of 
air movement. The specified CFM varies from locale to locale. 
Consult your HVAC professional for specific requirements in  
your area.