KitchenAid 30-Inch 4 Burner Gas Rangetop, Commercial-Style Installation Guide
14
GAS CONVERSIONS
IMPORTANT: Gas conversions from Natural gas to LP gas must
be done by a qualified installer.
LP Gas Conversion
1. Turn the manual shut-off valve to the closed position.
2. Unplug cooktop or disconnect power.
To Convert Gas Pressure Regulator
1. Remove the access cap by using a wrench, turning the
access cap counterclockwise.
2. Remove spring retainer from the cap by pushing against the
flat side of the spring retainer. Look at the spring retainer
to locate the “NAT” or “LP” position. Turn over the spring
retainer so the “LP” is showing on the bottom. Snap the
spring retainer back into the cap. Reinstall the cap onto the
regulator.
3. Test the gas pressure regulator and gas supply line.
The regulator must be checked at a minimum 1" (2.5 cm)
water column above the set pressure. The inlet pressure
to the regulator should be as follows for operation and
checking the regulator setting:
LP Gas:
Minimum pressure 11" (27.9 cm) WCP
Maximum pressure 14" (35.5 cm) WCP
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least
LP Gas:
Minimum pressure 11" (27.9 cm) WCP
Maximum pressure 14" (35.5 cm) WCP
Gas Supply Pressure Testing
Gas supply pressure for testing regulator must be at least
1" water column pressure above the manifold pressure
shown on the model/serial/rating plate.
Line pressure testing above
Line pressure testing above
1
/
2
psi gauge (14" WCP)
The cooktop and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of
1
/
2
psi (3.5 kPa).
Line pressure testing at
1
/
2
psi gauge (14" WCP) or lower
The cooktop must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than
1
/
2
psi (3.5 kPa).
To Convert Surface Burners
1. If installed, remove the burner grates.
2. Remove burner cap.
3. Remove the burner base.
2. Remove burner cap.
3. Remove the burner base.
A
B
Large Dual Burner
A. Burner cap
B. Burner base
A. Burner cap
B. Burner base
A
B
C
Medium Burner
A. Burner cap
B. Burner base
C. Choke (for use with medium
A. Burner cap
B. Burner base
C. Choke (for use with medium
burner, LP gas only)
A
B
Small Burner
A. Burner cap
B. Burner base
A. Burner cap
B. Burner base
WARNING
Explosion Hazard
Use a new CSA International approved gas supply line.
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure
Install a shut-off valve.
Securely tighten all gas connections.
If connected to LP, have a qualified person make sure
gas pressure does not exceed 14" (36 cm) water
column.
Examples of a qualified person include:
licensed heating personnel,
Examples of a qualified person include:
licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.
Failure to do so can result in death, explosion, or fire.
Failure to do so can result in death, explosion, or fire.
A
B
C
A. To cooktop
B. Shut-off valve (closed position)
C. Gas supply line
B. Shut-off valve (closed position)
C. Gas supply line
A
B
C
D
E
A. Access cap
B. Gasket
C. Gas pressure regulator
B. Gasket
C. Gas pressure regulator
D. LP position
E. NAT position
E. NAT position