CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM/PDU/DISTRIBUTION 
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 
2
C. 
Where applicable, the UPS shall also be designed in accordance with publications from 
the following organizations and committees 
 
1. 
NFPA- National Fire Protection Associations 
 
2. 
NEMA - National Electrical Manufacturers Association 
 
3. 
OSHA - Occupational Safety and Health Administration 
D. 
IEEE 519-1992 Standard Practices and Requirements for Harmonic Control in 
Electrical Power Systems. 
E. 
ISO 9001 
F. 
ISO 14001 
1.3 
UPS MODES OF OPERATION 
A. 
Normal: The input converter and output inverter shall operate in an on-line manner to 
continuously regulate power to the critical load. The input and output converters shall 
be capable of full battery recharge while simultaneously providing regulated power to 
the load for all line and load conditions within the range of the UPS specifications.  
B. 
Battery: Upon failure of the AC input source, the critical load shall continue being 
supplied by the output inverter, which shall derive its power from the battery system. 
There shall be no interruption in power to the critical load during both transfers to 
battery operation and retransfers from battery to normal operation.  
C. 
Recharge: Upon restoration of the AC input source, the input converter and output 
inverter shall simultaneously recharge the battery and provide regulated power to the 
critical load.  
D. 
Static Bypass: The static bypass shall be used to provide transfer of critical load from 
the Inverter output to the bypass source. This transfer, along with its retransfer, shall 
take place with no power interruption to the critical load. In the event of an emergency, 
this transfer shall be an automatic function. 
E. 
Maintenance Bypass: The system shall be equipped with an external make-before-break 
Maintenance Bypass Cabinet (MBC) to electrically isolate the UPS during routine 
maintenance and service of the UPS. The MBC shall completely isolate both the UPS 
input and output connections. 
1.4 
SUBMITTALS 
A. 
Proposal Submittals: 
 
1. 
As bid system bill of materials.