Honeywell Bypass Drum Humidifier (HE120A) Installation Instruction

Page of 48
HE120 BY-PASS DRUM HUMIDIFIER
69-1860EF—01
8
4.
Pre-drill the mounting holes using a 1/8 in. drill bit. If you 
are installing the optional Damper, do not drill the hole 
where the damper blade will swing. See Fig. 10. 
Fig. 10. Drill pattern.
5.
If you are installing the Optional Damper, place a #8 X 
3/4 in. Sheet Metal Screw through the Bypass Collar 
and Damper, as shown in Figure 11.
Fig. 11. Installing Optional Damper.
6.
Place the Damper into position and install using 
#8 x 3/4 in. Sheet Metal Screws.
7.
If you installed the optional Damper, check that it opens 
and closes correctly. (If necessary, tighten or loosen the 
pivot screw to make it open and close correctly.)
NOTE:
The Damper will not cover all of the opening in the 
duct when closed. A small amount of leakage when 
closed is acceptable.
OPTIONAL
DAMPER
PIVOT 
POINT
BYPASS
COLLAR
DO NOT DRILL 
THIS SCREW 
LOCATION 
IF OPTIONAL 
DAMPER IS USED
M13615
CLOSE
OPEN
BENT UP EDGE OF 
DAMPER
SHEET METAL 
SCREW (PIVOT SCREW)
HOLE IN 
DAMPER
FLAT SIDE 
OF BYPASS 
COLLAR
M13621