Cisco Optical Hub and Hub-Node Installation Guide

Page of 162
 
Chapter 3    Setup and Operation 
 
 
 
58 
OL-29936-01 
[1]  This alarm sets the unit to the safe state.  In the safe state the amplifier is turned 
off causing the optical amplifier output to be disabled. 
[2]  This alarm tests for presence of +24V, -6V from the OIB. 
[3]  This alarm indicates the state of the internal voltages (+24V, +5.0V, Vref). 
[4]  See following for laser nominal set point temperature based on module 
temperature. 
[5]  See next table for input power alarm values. 
Input Power Alarm Parameters 
The following tables define the input power alarm parameters for the EDFA. 
Gain Flattened EDFA - Constant Gain Mode (Default) 
 
Product Type 
Major 
High 
Minor 
High 
Minor 
Low 
Major 
Low 
Values 
Typical 
Value 
Hysteresis 
Units 
17.0 / 21.0 dBm 
Low Gain 
45.0 
25.0 
-8.0 
-10.0 
Ok 
Alarm 
-7.0 
0.1 
dBm 
17.0 / 21.0 dBm 
High Gain 
45.0 
25.0 
-13.0 
-15.0 
Ok 
Alarm 
-12.0 
0.1 
dBm 
 
Gain Flattened EDFA - Constant Power Mode 
 
Product Type 
Major 
High 
Minor 
High 
Minor 
Low 
Major 
Low 
Values 
Typical 
Value 
Hysteresis 
Units 
17.0 / 21.0 dBm 
Low/High Gain 
45.0 
25.0 
-10.0 
Ok 
Alarm 
5.0 
0.1 
dBm 
 
Broadcast EDFA - Constant Power Mode (Default) 
 
Product Type 
Major 
High 
Minor 
High 
Minor 
Low 
Major 
Low 
Values 
Typical 
Value 
Hysteresis 
Units 
17.0/20.0/22.0 
dBm 
45.0 
25.0 
-10.0 
Ok 
Alarm 
5.0 
0.1 
dBm 
 
Broadcast EDFA - Constant Gain Mode 
 
Product Type 
Major 
High 
Minor 
High 
Minor 
Low 
Major 
Low 
Values 
Typical 
Value 
Hysteresis 
Units 
17.0/20.0/22.0 
dBm 
45.0 
25.0 
-13.0 
-15.0 
Ok 
Alarm 
-12.0 
0.1 
dBm