External Alarms Connections 
 
78-4025693-01 Rev D 
25 
 
External Alarms Connections 
Master-Slave Operation 
All Prisma II modules ship from the factory configured as a “master.” They can be 
reconfigured as "slave" or redundant modules through command line interface (CLI) 
commands. The chassis allows for local hard-wired redundancy by using the 
ALARM IN and ALARM OUT connectors on the connector interface panel. With 
these connectors, a master-slave pair of modules can be configured so that if the 
master fails, the slave takes over. 
 
ALARMS IN and ALARMS OUT Connections 
The chassis provides two connections for external alarms to and from each module 
slot. These alarm connections are located in two 37-pin D-connectors (DB-37) labeled 
ALARMS IN and ALARMS OUT. 
When a critical alarm occurs in a master module, the master turns off and the slave 
(redundant module) is enabled. To make this happen, the pin representing the 
master module slot in the ALARM OUT connector must be externally wired to the 
pin representing the slave module slot in the ALARM IN connector. 
Important: 
 
This module takes up two slots in the Prisma II chassis. For purposes of 
redundancy wiring, the module is identified with the higher-numbered slot. For 
example, if the module occupies slots 6 and 7 (module ejector lever at slot 6), its 
ALARM IN and ALARM OUT connections are made at slot 7, and the pins for 
slot 6 are not used. 
 
Any device configured as a master ignores its own ALARM IN contacts. 
 
To verify proper wiring and redundant configuration, unplug the master device 
and confirm that the slave module turns on as a result. 
 
Once the ALARM IN and ALARM OUT contacts are wired, take care to ensure 
that the master and slave modules are not moved to other slots. If they are, the 
ALARM IN and ALARM OUT connectors will need to be rewired to the 
appropriate pins.