Moxa M-4202 User Manual

Page of 14
 www.moxa.com     email: info@moxa.com     
5-5-36
 www.moxa.com     email: info@moxa.com     
Remote Monitoring Solutions
5-36
5
Remote I/O  
>
Digital Output Modules
M-2600
  16 digital outputs, sink, 24 VDC, 0.3A
Outputs per Module: 16 points, sink type
Output Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDC
On-state Voltage Drop: Max. 0.3 VDC @ 25°C
On-state Current: Min. 1 mA per channel
Off Leakage Current: Max. 50 µA
Output Current Rating: Max. 0.3A per channel 
Max. 4A per common
Common Type: 16 points / 2 COM (single common)
Power Consumption: Max. 80 mA @ 5 VDC
 
16-channel digital output modules
24V
24V
0V
0V
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Ch0
0     1
18   19
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (0 VDC)
Field Power (24 VDC)
L
L
L
L
L
L
L
L
M-2600
Status
3 71115
2 61014
1 5 9 13
0 4 8 12
24V
24V
0V
0V
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Ch0
0     1
18   19
System Power (5 VDC)
System Power (GND)
System Bus
Field Power (0 VDC)
Field Power (24 VDC)
L
L
L
L
L
L
L
L
M-2601
Status
71115
61014
1 5 9 13
0 4 8 12
M-2601
 16 digital outputs, source, 24 VDC, 0.3A
Outputs per Module: 16 points, source type
Output Voltage Range: 24 VDC nominal, min. 11 VDC to max. 28.8 VDC
On-state Voltage Drop: Max. 0.3 VDC @ 25°C
On-state Current: Min. 1 mA per channel
Off Leakage Current: Max. 50 µA
Output Current Rating: Max. 0.3A per channel 
 Max. 4A per common
Common Type: 16 points / 2 COM (single common)
Power Consumption: Max. 80 mA @ 5 VDC