APC G7TUPS250 User Manual

Page of 6
(1)Depending on load level.  (2). 8 hours max., 35°C continuous.  (3). 160 and 200kVA not included
Rated power (kVA)
160
200
250
300
400
500
Normal AC input
Input voltage range
250 V(1) to 470 V, three phase
Normal and bypass AC inputs
Separate
Frequency
45 Hz to 66 Hz
Input current distortion (THDI)
< 5 %
Input power factor
> 0.99
Phase sequence detection
Yes
Bypass AC input
Input voltage range
(380 V, 400 V, 415 V, 440 V) +/- 10%
Frequency
50 Hz / 60 HZ +/- 10%
Output
Power factor
0.9
Phase-to-phase voltage 
setting
380/400/415/440 V, three-phase + neutral
Voltage regulation
- 1%
Frequency
50 or 60 Hz +/- 0.1%
Permissible overloads
150% for 30 s, 125% for 10 minutes
Voltage distortion (THDU)
< 2% Ph/Ph and Ph/N for non-linear loads
Battery
Number of battery chains 
managed
Up to 2 circuit breakers
Type
Sealed lead-acid, vented, Ni-Cd
Overall efficiency
Double conversion
Up to 94.5%
Environmental conditions
Operating temperature
Up to 40°C (2)
Humidity
Up to 95% (non-condensing)
Operating altitude
Up to 1000 m, without derating
Color
RAL 9023
IP degree of protection
IP20 Standard, IP32 Optional
Parallel configurations 
Integrated parallel units
Up to 8 units
Parallel modules with remote 
centralized static bypass 
switch (3)
Up to 8 units
Standards
Construction and safety
IEC/EN 62040-1, IEC/EN 60950
Performance and topology
IEC 62040-3
Design and manufacture
ISO 14001, ISO 9001, IEC 60146
EMC immunity
IEC61000-4
EMC emissions
IEC 62040-2 C3
Approvals
LCIE - CE Mark
UPS dimensions (depth 855 mm, height 1900 mm)
Rated power (kVA)
160
200
250
300
400
500
Width (without battery, in mm)
1412
1812
Weight (in kg)-note 5
840
990
1140
1500
Technical characteristics