See Figure 1 for systems applicable to the UPS system. 
 
 
 
 
 
 
 
 
 
 
 Figure 1. Block diagram 
 
•  An input filter reduces transients on the main supply. 
•  For maintaining full battery charge, AC power is rectified and regulated in the 
rectifier feeding power to the inverter and battery converter. 
•  DC power is converted to AC in the inverter and passes it on to the load. 
•  Power to the load is maintained from the battery during a power failure. 
•  The converter increases voltage for the inverter as required. 
 
2.2 
Efficiency Optimizer Function 
The Efficiency Optimizer function is a new feature for the UPS that increases the cost 
effectiveness of the UPS by minimizing power losses and reduces power consumption. 
Alternating between bypass and on-line modes is achieved automatically and in 
accordance with the conditions of the utility power. On-line mode may be used during 
times of utility power irregularities. The bypass mode should be used when power flows