Enviro sienna indoor gas fireplace User Manual

Page of 32
25
Trouble Shooting
Problem
Possible Cause
Solution
The  main  burner 
does  not  ignite 
when called for.
The gas valve may not be on.
• Check that the gas control knob is in the “ON” position.
Thermostat is not calling for 
heat.
• Adjust the thermostat several degrees above ambient temperature.
Problem with gas valve.
• Use a DC voltmeter to measure the voltage across the TPTH and 
TP terminals. Main operator voltage: Open circuit ≥ 325mV Closed 
circuit ≥ 100mV
• If voltage is not present, check the control circuit for proper 
operation.
• If proper control system voltage is present, replace the gas control.
Spark will not 
light the pilot 
after repeatedly 
pressing the 
spark ignitor.
Defective piezo ignitor.
• Check connections to ignitor.
• If ignitor connections are good but no spark, replace ignitor.
Broken spark electrode.
• Check for broken ceramic insulation, replace electrode if broken.
Misaligned spark electrode.
• If spark is not arcing from electrode to pilot, loosen the screws on the 
pilot base adjust and tighten.
Pilot will not 
remain lit.
Problem with thermocouple 
circuit.
• Check for proper connection of the thermocouple to the rear of the 
valve. If loose, fully tighten.
• Check pilot for full flame impingement around thermocouple.  If flame 
is too small, check gas pressure, adjust pilot rate screw, check pilot 
head for damage.
• Check thermocouple voltage at valve. It must be greater than 5 mV.  
If low, replace thermocouple.
Air in gas line (pilot dies while 
knob is depressed).
• Bleed line.
• Check gas line pressure.
• Contact dealer.
Burners will not 
remain lit.
Problem with thermopile 
circuit.
• Check gas line pressure .
• Check for flame impingement on thermopile. If low, see “Pilot will not 
remain lit”.
• Check thermopile for minimum of 300 mV when burner is switched 
on.
• Check wiring to thermostat for breaks.
BV ONLY: Check for spillage at draft hood that may trip spill switch
Flame lifting
Leak in vent pipe
• Check for leaks in vent connections.
Improper vent configuration
• Check vent configuration with manual.
Terminal may be recirculating 
flue gases
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
Glass fogs up
Normal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
Blue Flames
Normal during start up: flames will yellow as the fireplace heats up.
Flames are 
burning “dirty” or 
sooting
Flame impingement
• Check log positioning.
• Increase primary air by opening the venturi shutter and/or by 
opening the vent restrictor.
See also “Burners will not remain lit.”
Remote control 
doesn’t work
Problem with the remote
• One or more of the batteries are dead. See remote control 
instructions.
Problem with fireplace
• The on/off switch is turned to OFF.
• The gas control valve is turned to PILOT or OFF.
• The pilot has gone out.
BV ONLY: 
Insufficient air 
for combustion
• Air tight house.
•  A  vacuum  in  room  due  to 
other air-moving device.
• Supply make up air to the unit.