(b)  For  buildings  with  vinyl  siding,  a  vinyl  siding  standoff, 
should  be  installed  between  the  vent  cap  and  the  exterior 
wall  (see  Figure  29).  Attach  the  vinyl  siding  standoff  to  the 
horizontal  termination.  The  vinyl  siding  standoff  prevents 
excessive heat from possibly melting the vinyl siding material. 
Note that the horizontal vent termination bolts onto the flat 
portion of the vinyl siding standoff (shaded area in Figure 29), 
so that an air space will exist between the wall and the vent 
termination.
(c) The horizontal run of vent pipe must be level and should 
have  a  11⁄4  inch  (32mm)  rise  for  every  one  foot 
(305mm) of run towards the termination. Never  allow 
the vent to run downward. This could cause high temperature 
and may present the possibility of a fire.
(d)  The  location  of  the  horizontal  vent  termination  on  the 
exterior wall must not be easily blocked or obstructed. 
(e)  When  installing  a  vent  pipe  in  a  chase  the  minimum 
clearance to combustibles is 2” (51 mm).
(f) Maintain manufacturer’s clearances to combustibles with 
venting.
Initial Installation
QUALIFIED INSTALLERS ONLY
Figure 32: Installation for Cara DR with a 
snorkel.
If  necessary  to  get  above  grade  the  Cara  DR  can  be 
installed using a 14” or 36” snorkel.
Place the unit into position.
Attach a small section of pipe on the unit and mark exterior 
wall where vent would pass through the wall.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain 
clearances to combustibles. Frame hole as shown in Figure 
27.
Install a wall thimble, interior finished collar, and the vent 
section through the wall.
Seal around the vent terminal to the structure using a non-
hardening mastic.
Also refer to I
NITIAL
 I
NSTALLATION
 - I
NSTALLATION
 
OF
 A
PPLIANCE
.
I
NSTALLATION
 
WITH
 O
PTIONAL
 S
NORKEL
:
Figure 31: Installation for Cara DR.