Initial Installation
C
OMMONWEALTH
 
OF
 M
ASSACHUSETTS
 I
NSTALLATION
 A
DENDUM
:
These are the Special Requirements for Side-Wall Vented Appliances in Commonwealth of 
Massachusetts
IMPORTANT: The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 
and 5.00 for installation of side-wall vented gas appliances as follows:
(a) For  all  side  wall  horizontally  vented  gas  fueled  equipment  installed  in  every  dwelling,  building  or 
structure used in whole or in part for residential purposes, including those owned or operated by the 
Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above 
finished grade in the area of the venting, including but not limited to decks and porches, the following 
requirements shall be satisfied:
1.  INSTALLATION OF CARBON MONOXIDE DETECTORS.  At the time of installment of the 
side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe 
that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on 
the floor level where the gas equipment is to be installed.  In addition, the installing plumber or 
gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an 
alarm is installed on each additional level of the dwelling, building or structure served by the side 
wall vented gas fueled equipment.  It shall be the responsibility of the property owner to secure 
the services of qualified licensed professionals for the installation of hard wired carbon monoxide 
detectors.
a.   In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl 
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up 
may be installed on the next adjacent floor level.
b.  In the event that the requirements of this subdivision can not be met at the time of completion 
of installation, the owner shall have a period of thirty (30) days to comply with the above 
requirements; however, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.
2.  APPROVED CARBON MONOXIDE DETECTORS.  Each carbon monoxide detector as required 
in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed 
and IAS certified.
3.  SIGNAGE.  A metal or plastic identification plate shall be permanently mounted to the exterior 
of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust 
vent terminal for the horizontally vented gas fueled heating appliance or equipment.  The sign 
shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.  
KEEP CLEAR OF ALL OBSTRUCTIONS.”
4.  INSPECTION.  The state or local gas inspector of the side wall horizontally vented gas fueled 
equipment  shall  not  approve  installation  unless,  upon  inspection,  the  inspector  observes 
carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 
5.08(2)(a)1 through 4.