Chapter 7. PARAMETER SETUP
7-8
No.
Item Code
Item
Factory
User
Setting
Setting
Setting
12
G 5 .T
2.0
13
C P . 1  1
0U
14
C P . 1 2
200U
15
C P . 1 3
400U
16
C P . 1 4
600U
17
C P . 1 5
800U
18
C P . 1 6
1000U
19
C P . 1 7
1200U
20
F A S T
0
21
D 1  F F
5U
5.0
0.0
22
C Y . 1
10
23
C Y . 2
10
24
C Y . 3
25
D V -L
5U
26
D V -H
5U
27
H Y -L
5U
28
H Y -H
5U
0.1 to 60.0s
-1999 to 9999U
[Note]
When setup data 
C
  
1
  
1
 setting is 0 (PID set auto-
switching OFF), “– – – –” is displayed and setting is not
possible.
-1999 to 9999U
[Note]
On heat/cool models, “– – – –” is displayed and setting
is not possible.
On other models, when setup data  
C
  
1
  
1
 setting is 0
(PID set auto-switching OFF), “– – – –” is displayed
and setting is not possible.
0: 2X
1: 10X
2: 60X (10X)
3: 120X (10X)
[Note]
When setup data 
C
 
6
 
4
 setting is 1 (program time
unit:min/s), the FAST factor is 10X for settings 2 and 3.
0 to 1000U
[Note]
This setting is displayed on 0D and 6D models.
0.5 to 25.0%
[Note]
This setting is displayed on 2G output models.
-100.0 to 50.0%
[Note]
This setting is displayed on heat/cool models.
[Note]
On 5G output models, “– – – –” is displayed and
setting is not possible.
5 to 120s (relay output)
1 to 60s (voltage output)
[Note]
On models whose output 1 is neither relay output nor
voltage output, “– – – –” is displayed and setting is not
possible.
5 to 120s (relay output)
1 to 60s (voltage output)
[Note]
On models whose output 2 is neither relay output nor
voltage output, “– – – –” is displayed and setting is not
possible.
[Note]
“– – – –” is displayed and setting is not possible.
0 to 1000U
[Note]
On models other than 3D output models, “– – – –” is
displayed and setting is not possible.
G.Soak time (CH1)
PID auto-switching
point 1-1
PID auto-switching
point 1-2
PID auto-switching
point 1-3
PID auto-switching
point 1-4
PID auto-switching
point 1-5
PID auto-switching
point 1-6
PID auto-switching
point 1-7
FAST factor
ON-OFF control
differential
Position-propor-
tional dead zone
Heat/cool control
dead zone
Output 1 time-
proportional output
cycle
Output 2 time-
proportional output
cycle
Unused
3-position control
deviation lower limit
3-position control
deviation upper limit
3-position control
lower limit hyster-
esis
3-position control
upper limit hyster-
esis