Alliance Laundry Systems T433I User Manual

Page of 116
Gas Requirements
39
M414038
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Table 7 
Gas Pipe Size Required for 1000 Btu Natural Gas – .64 Specific Gravity
at 7 to 9 inches Water Column Pressure (1.74 ± 2.241 kPa) 
Equivalent Length
Gas 
Appliances 
Total 
Btu/hr.
25 feet 
(7.63 m)
50 feet
(15.25 m)
75 feet
(22.88 m)
100 feet
(30.50 m)
125 feet
(38.13 m)
150 feet
(45.75 m)
Based on 0.3 in. Water Column Pressure Drop for Length Given
Sizes shown in inches (mm)
300,000
400,000
500,000
600,000
700,000
800,000
900,000
1,000,000
1,100,000
1,200,000
1,300,000
1,400,000
1,500,000
1,600,000
1,700,000
1,800,000
1,900,000
2,000,000
2,200,000
2,400,000
2,600,000
2,800,000
3,000,000
3,200,000
3,400,000
3,600,000
3,800,000
4,000,000
1 (25.40)
1.25 (31.75)
1.25 (31.75)
1.5 (38.10)
1.5 (38.10)
1.5 (38.10)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
1.25 (31.75)
1.25 (31.75)
1.5 (38.10)
1.5 (38.10)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
1.25 (31.75)
1.5 (38.10)
1.5 (38.10)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
1.5 (38.10)
1.5 (38.10)
2 (50.80)
2 (50.80)
2 (50.80)
2 (50.80)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
4 (101.60)
4 (101.60)
1.5 (38.10)
1.5 (38.10)
2 (50.80)
2 (50.80)
2 (50.80)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
4 (101.60)
4 (101.60)
4 (101.60)
4 (101.60)
1.5 (38.10)
2 (50.80)
2 (50.80)
2 (50.80)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
2.5 (63.50)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3 (76.20)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
3.5 (88.90)
4 (101.60)
4 (101.60)
4 (101.60)
4 (101.60)
4 (101.60)
4 (101.60)
FOR L.P. (LIQUEFIED PETROLEUM) GAS, CORRECT THE TOTAL BTU/HR. BY MULTIPLYING IT BY 0.6. 
THE ANSWER IS THE EQUIVALENT BTU ON THE ABOVE CHART.
IMPORTANT: The installation must conform with local codes or, in the absence of local codes:
with the latest edition of the “National Fuel Gas Code,” ANSI Z223.1/NFPA 54 in the U.S.A.,
with CSA-B149.1 or Natural Gas and Propane Installation Code in Canada,
and Australian Gas Association/Australian L.P. Gas Association requirements in Australia.