APC galaxy 9000 User Manual

Page of 40
34006451EN/AC
 - Page 5
Characteristics
1.2 Rectifier-inverter cubicle 
Characteristics of rectifier-inverter cubicles
1.3 Static Switch Cubicle
Characteristics of Static Switch Cubicles 
The parameters given in the table opposite can be used to determine the required rating of a single-unit or modular UPS, a 
frequency converter, or a parallel UPS with SSC.
rated
inverter
output
in kVA
cubicle
width W
in mm (1)
cubicle
height H
in mm
cubicle
depth D
in mm
maximum
weight
in kg
heat losses (2)
in kW
in cal./s
800
3600 ±10
2000
840
4260
47
11233
900
3600 ±10
2000
840
4260
47
11233
(1) the width of the vertical side clearance bars (25 mm) on each side must be added to the indicated cubicle width, i.e. 50 mm in 
all per cubicle. This applies to all cubicle installation cases. Cubicle widths have been rounded off to the nearest cm.
(2) the indicated heat losses are those produced by the unit at full rated load and with the battery float charging. They must be 
taken into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation.  
The air enters via the doors and grids at the bottom and is discharged via the roof.
rated
SSC
output
in kVA
cubicle
width W
in mm (1)
cubicle
height H
in mm
cubicle
depth D
in mm
maximum
weight
in kg
heat losses (2)
in kW
in cal./s
2000
2450 ±10
1900 ±10
840
1710
< 0.5
< 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This applies to all cubicle 
installation cases. Cubicle widths have been rounded off to the nearest cm.
(2) the indicated heat losses are those produced by the unit at full rated load when operating on Mains 2. They are not to be taken 
into account when dimensioning the air conditioning system. The cubicles are cooled by forced ventilation.