temco-tool 36tdvn User Manual

Page of 44
27
TDVN Series Direct Vent Gas Fireplace
20007636
   
Defective thermo-generator.   
After the pilot has been lit for approximately three minutes,  
   
(Millivolt system) 
and only the thermo-generator wire connected to the main  
   
 
operator head, measure the voltage across TPTH and TP.   
   
 
This open circuit voltage should be between 500mv and    
   
 
750mv. Tune the pilot adjustment screw until the mv reading  
   
 
falls within these parameters. (Counter-clockwise increases  
   
 
mv reading, clockwise decreases)
   
Defective safety magnet. 
Verify operation of safety magnet in the following   
   
(mv Plus systems) 
manner. 
 
 
 
 
 
 
   
 
(A)  Depress and hold pilot button. 
 
 
 
   
 
(B)  Verify open-circuit thermocouple voltage as de 
 
   
 
 
scribed in previous step.   
 
 
 
   
 
(C)  Reconnect thermocouple to valve.   
 
 
   
 
(D)  Measure the Millivoltage between the solder button    
   
 
on the base of the safety magnet, and the valve    
 
   
 
body.  If the mv reading is above 6mv for vented    
 
   
 
appliances, or 8.5 mv for un-vented appliances, and  
 
   
 
the safety magnet does not hold, replace the valve.  
 
   
 
(E)  If closed circuit mv reading is the same as the open    
   
 
circuit reading, the coil is electrically open.  Replace  
 
   
 
the valve.
   
Defective Safety Magnet  
Verify operation of safety magnet in the following   
 
   
(Millivolt system) 
manner. 
 
 
 
 
 
 
   
 
(A)  Remove all wires from the terminals of the main  
 
   
 
 
operator.  
 
 
 
 
 
   
 
(B)  Measure the electrical voltage between the termi 
 
   
 
nals TPTH and TP. If the voltage is above 110mv   
 
   
 
and the safety magnet does not hold, replace the   
 
   
 
valve.
   
Pilot orifice blocked. 
Replace orifice with a new orifice of the exact size and  
 
   
 
type.
  Pilot drops out. 
Wrong pilot orifice. 
Replace the orifice with a new orifice supplied specifi 
 
   
 
cally for the appliance and gas type in question.
  No gas to main burner 
Low gas pressure to appliance. 
With the main burner functioning, adjust the inlet pres 
 
   
 
sure regulator to supply gas to the appliance within the  
 
   
 
design parameters of the appliance manufacturer.   
 
   
 
(Typically 7”NG, 11”LPG).
   
Pilot not lit. 
Light pilot and wait for thermo-generator to heat up  
 
   
 
sufficiently to power the main operator.  If pilot fails to  
 
   
 
light, or hold, refer to above sections.
   
Control knob not in ON  
Rotate OFF/PILOT/ON control knob to the ON position. 
 
   
 
position.
  Thermostat/wall switch  
Thermostat not in ON position. 
Turn thermostat ON, and adjust temperature control to  
 
  will not cycle main  
 
call for heat.   
 
 
 
 
 
  burner.  
System Checks 
(continued)
  Problem 
Possible Cause 
Solution